Topology: Serial Number Different - Siemens SINAMICS S210 Operating Instructions Manual

Servo drive system
Hide thumbs Also See for SINAMICS S210:
Table of Contents

Advertisement

Cause:
The topology comparison has detected differences in the actual topology and target topologies in the electronic rating plate.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex: aa = component number (%1), bb = component class of the target topology (%2), cc = component class
of the actual topology (%3), dd = difference (%4)
dd = 01 hex = 1 dec:
Different component type.
dd = 02 hex = 2 dec:
Different article number.
dd = 03 hex = 3 dec:
Different manufacturer.
dd = 04 hex = 4 dec:
For a multi-component slave, the incorrect subcomponent (index) is connected (e.g. Double Motor Module X201 instead
of X200) - or only a part of a multi-component slave is set to "deactivate and not available".
dd = 05 hex = 5 dec:
NX10 or NX15 used instead of CX32.
dd = 06 hex = 6 dec:
NX10 or NX15 used instead of CX32.
dd = 07 hex = 7 dec:
Different number of connections.
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- connect the expected component (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
Topology comparison - if required, adapt the comparison level:
- parameterize the topology comparison of all components (p9906).
- parameterize the topology comparison of one components (p9907, p9908).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
A01425

Topology: Serial number different

Message value:
Component: %1, %2, differences: %3
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to one component. The
serial number is different.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = reserved
cc = number of differences (%3)
bb = component class (% 2)
aa = component number (%1)
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
Faults and alarms
13.2 List of faults and alarms