F30058 (N, A) Power Unit: Heat Sink Fan Defective; Precharge Contactor State Monitoring - Siemens SINAMICS S210 Operating Instructions Manual

Servo drive system
Hide thumbs Also See for SINAMICS S210:
Table of Contents

Advertisement

Cause:
Frequencies have been detected on the DC link voltage that would suggest line asymmetry or failure of a line phase.
It is also possible that a motor phase has failed.
Fault F30011 is output if the alarm is present and at the latest after 5 minutes.
The precise duration depends on the power unit type and the particular frequencies. For booksize and chassis power units,
the duration also depends on how long the alarm has been active.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the line phase connection.
- check the motor feeder cable connections.
If there is no phase failure of the line or motor, then line asymmetry is involved.
- reduce the power in order to avoid fault F30011.

F30058 (N, A) Power unit: heat sink fan defective

Message value:
-
Drive object:
All objects
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
The feedback signal from the heat sink fan signals a fault.
- fan defective.
- fan blocked.
- feedback signal inaccurate.
Remedy:
- check the heat sink fan and replace if necessary.
- if you are using an external fan with feedback signal, check its wiring (X12.2 or X13.2).
Note:
If you are using an external fan without feedback signal, check that the feedback terminal wiring at the power unit is
connected to ground and make this connection if necessary (X12.1/2 or X13.1/2).
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F30059
Power unit: Internal fan faulty
Message value:
-
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The internal power unit fan has failed and is possibly defective.
Remedy:
Check the internal fan and replace if necessary.
F30060 (A)

Precharge contactor state monitoring

Message value:
Fault cause: %1 bin
Drive object:
All objects
Reaction:
OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
Faults and alarms
13.2 List of faults and alarms