Faults and alarms
13.2 List of faults and alarms
Remedy:
Use power units with the same code number.
For parallel circuit configurations, only power units with identical power unit data may be used.
F05056

Parallel circuit: Power unit EEPROM versions differ

Message value:
Parameter: %1
Drive object:
All objects
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the power units do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
Use power units with the same EEPROM version.
Note:
For parallel circuit configurations, only power units with identical EEPROM versions may be used.
F05057

Parallel circuit: Power unit firmware versions differ

Message value:
Parameter: %1
Drive object:
All objects
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the power units connected in parallel do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
Use power units with the same firmware version.
For parallel circuit configurations, only power units with identical firmware versions may be used.
F05058

Parallel circuit: VSM EEPROM versions differ

Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The EEPROM versions of the Voltage Sensing Modules (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical EEPROM versions may be used.
F05059

Parallel circuit: VSM firmware versions differ

Message value:
Parameter: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The firmware versions of the Voltage Sensing Module (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy:
For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical firmware versions may be used.
F05060
Parallel circuit: Power unit firmware version does not match
Message value:
Parameter: %1
Drive object:
All objects
422
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA