Faults and alarms
13.2 List of faults and alarms
Cause:
The system has identified that two motor data sets were incorrectly parameterized.
Parameter r0313 (calculated from p0314, p0310, p0311), r0315 and p1982 may only have different values if the motor
data sets are assigned different motors. p0827 is used to assign the motors and/contactors.
It is not possible to toggle between motor data sets.
Fault value (r0949, interpret hexadecimal):
xxxxyyyy:
xxxx: First DDS with assigned MDS, yyyy: Second DDS with assigned MDS
Remedy:
Correct the parameterization of the motor data sets.
A07519

Drive: Motor changeover incorrectly parameterized

Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
With the setting p0833.0 = 1, a motor changeover via the application is selected. This is the reason that p0827 must have
different values in the appropriate motor data set.
Alarm value (r2124, interpret hexadecimal):
xxxxyyyy:
xxxx: First MDS, yyyy: Second MDS
Remedy:
- parameterize the appropriate motor data sets differently (p0827).
- select the setting p0833.0 = 0 (motor changeover via the drive).
A07520

Drive: Motor cannot be changed over

Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The motor cannot be changed over.
Alarm value (r2124, interpret decimal):
1:
The contactor for the motor that is presently active cannot be opened, because for a synchronous motor, the speed (r0063)
is greater than the speed at the start of field weakening (p0348). As long as r0063 > p0348, the current in the motor does
not decay in spite of the pulses being suppressed.
2:
The "contactor opened" feedback signal was not detected within 1 s.
3:
The "contactor closed" feedback signal was not detected within 1 s.
Remedy:
For alarm value = 1:
Set the speed lower than the speed at the start of field weakening (r0063 < p0348).
For alarm value = 2, 3:
Check the feedback signals of the contactor involved.
A07530

Drive: Drive Data Set DDS not present

Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected drive data set is not available (p0837 > p0180). The drive data set was not changed over.
Remedy:
- select the existing drive data set.
- set up additional drive data sets.
452