Commissioning
A bus termination network for cable type A is integrated in the housing of the FBS-SUB-9-GS-DP-B
plug. The switch for the bus termination must be in the ON position.
Fig. 21: Circuit diagram for bus termination network for cable type A as per EN 50170, switch in Festo
plug in ON position
8.3.4

Setting DIL switches

You can set the following parameters with the DIL switches:
– Operating mode. The energy efficiency module only supports the Remote I/O operating mode.
– PROFIBUS address
– Diagnostics mode
1. Switch off the power supply.
2. Unscrew the retaining screws of the cover.
3. Remove the cover.
Ä The 3 DIL switches can now be set.
4. Set the operating mode with DIL switch 1.
5. Set a station number that is not yet allocated for the energy efficiency module with DIL switch
3 è Tab. 24 Setting station number and diagnostic mode, example.
6. Set the diagnostic mode with DIL switch 3.
7. Fit the cover.
8. Screw on the retaining screws hand-tight and then tighten to 0.4 Nm ± 10%.