System Design and Installation
Note 1. Use the same wire sizes and tightening torques for
Note 2. Connect special OMRON Power Cable to the Servomotor connection terminals.
Wire Sizes and Allowable Current
■
The following table shows the allowable current for when there are three wires.
●
600-V Heat-resistant Vinyl Wiring (HIV) (Reference Values)
AWG size
Nominal cross-
sectional area (mm
20
0.5
---
0.75
18
0.9
16
1.25
14
2.0
12
3.5
10
5.5
8
8.0
6
14.0
4
22.0
Terminal Block Wiring Procedure
■
Connector-type Terminal Blocks are used for Servo Drivers of 1.5 W or less (except for the R88D-
WN20H-ML2 to R88D-WN30H-ML2). The procedure for wiring these Terminal Blocks is explained
below.
Connector-type Terminal Block
1.Remove the Terminal Block from the Servo Driver.
!Caution
The Terminal Block must be removed from the Servo Driver before being wired.
The Servo Driver will be damaged if the wiring is done with the Terminal Block in
place.
Configuration
Conductive
2
2
resistance
)
(wires/mm
)
19/0.18
39.5
30/0.18
26.0
37/0.18
24.4
50/0.18
15.6
7/0.6
9.53
7/0.8
5.41
7/1.0
3.47
7/1.2
2.41
7/1.6
1.35
7/2.0
0.849
C
N
3
C
U
N
1
V
W
C
N
(Example: R88D-WN01H-ML2)
2
C
N
4
− 2
− 1
,
, B1, B2, and B3.
Allowable current (A) for ambient
( Ω /km)
30 ° C
6.6
8.8
9.0
12.0
23
33
43
55
79
99
Chapter 3
temperature
40 ° C
50 ° C
5.6
4.5
7.0
5.5
7.7
6.0
11.0
8.5
20
16
29
24
38
31
49
40
70
57
88
70
3-17