Figure 4-1 Configuration Menu
Note: When changing multiple safety parameters, the verification steps do not need to be completed immediately.
Part No. 750-263

1. Changing Parameter Settings

To access the CB Falcon configuration menu, press <Configure> on
the Status page.
Some parameters require a password entr y before allowing
changes. The <Login> button will appear when any password-
protected parameter is displayed on the screen. Default service level
password is 9220.
Press <Login> to display the alphanumeric keyboard. Enter
password and press <OK>
Change parameter settings by selecting the parameter on the page.
A dialog box appears with controls allowing the user to change the
selected value. Press <Clear> to clear the current value. Enter the
new value and press <OK> (press <Cancel> to leave the
parameter unchanged).
Figure 4-2 Parameter change dialog
Safety Parameters
When configuring safety parameters an additional verification step
is required to confirm the changes.
1. When a safety parameter is changed, the Safety Parameter Verification
page will appear. Press <Begin> to continue.
2. The affected parameter group will be displayed, showing current
parameter values and a prompt, "Are these parameters set to proper
values?". Press <Yes> to continue.
3. The screen will indicate RESET DEVICE NOW. Open the control panel
and press the RESET button on the CB Falcon controller (press and hold
for 3 seconds).
RESET must be pressed within 30 seconds to save changes.
Section 4 — CFC Commissioning
4-15