Table 4. CB Falcon Modbus register map
00B4
0180
00B5
0181
00B6
01820182
00B7
0183
00B8
0184
00B9
0185
00BA
0186
00BB
0187
00BC
0188
00BD
0189
00BE
0190
00BF
0191
00C0
0192
00C1
0193
00C2
0194
00C3
0195
00C4
0196
00C5
0197
00C6
0198
00C7
0199
00C8
0200
00C9
0201
00CA
0202
00CB
0203
00CC
0204
00CD
0205
00CE
0206
Alarm silence time
Power up with lockout
Reset and restart
Burner name
Installation data
OEM ID
OS number
Date code
Safety Processor build
Application Processor build R
Installer password
OEM password
MODULATION
CONFIGURATION
Modulation output
CH maximum modulation
rate
DHW maximum modulation
rate
Minimum modulation rate
Prepurge rate
Lightoff rate
Postpurge rate
CH forced rate
CH forced rate time
DHW forced rate
DHW forced rate time
Burner switch
Firing rate control
Manual firing rate
Analog output hysteresis
R/W
U16
0-600 minutes
R/W
U16
SAFETY parameter
0=Clear lockout on power-up (reset),
1=Do not clear lockout on power-up (preserve)
W
U16
Force soft reset of Falcon subsystems:
0=None,
1=Burner control,
2=Application,
3=Burner control & application,
4=Clear alert log
Successful login required before request is granted.
R/W
Variable length string (up to 20 characters)
R/W
Variable length string (up to 20 characters)
R/W
Variable length string (up to 20 characters)
R
Variable length string (up to 16 characters)
R
Variable length string (up to 10 characters)
R
U16
U16
W
To set new installer password (up to 20 characters).
Requires register access status (register 177) set to
Installer or higher.
W
To set new OEM password (up to 20 characters).
Requires register access status (register 177) set to
OEM or higher.
R/W
U16
SAFETY parameter
0=Fan PWM,
1=0-10V,
2=4-20mA
R/W
U16
c
RPM or %
R/W
U16
c
RPM or %
R/W
U16
c
RPM or %
R/W
U16
SAFETY parameter
c
RPM or %
R/W
U16
SAFETY parameter
c
RPM or %
R/W
U16
SAFETY parameter
c
RPM or %
R/W
U16
c
RPM or %
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
c
RPM or %
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
0=Off, 1=On. Used to enable/disable burner control.
R/W
U16
0=Auto,
1=Manual in Run,
2=Manual in Run & Standby
R/W
U16
Firing rate used when control is set to manual (% or
c
RPM
)
R/W
U16
0-10V/4-20mA modulation output hysteresis. Setting of
0-10.
13