Table 4. CB Falcon Modbus register map
01E5
0485
01E6
0486
01E7
0487
01E8
0488
01E9
0489
01EA
0490
01EB
0491
01EC
0492
01ED
0493
01EE
0494
01EF
0495
01F0
0496
01F1
0497
01F2
0498
01F3
0499
01F4
0500
01F5
0501
01F6
0502
01F7
0503
Delta-T retry limit
Delta-T rate limit enable
Delta-T inverse limit time
Delta-T inverse limit
response
Delta-T exchanger/outlet
enable
Delta-T exchanger/outlet
degrees
Exchanger T-rise enable
T-rise response
T-rise retry limit
Delta-T inlet/exchanger
enable
Delta-T inlet/exchanger
degrees
ANTICONDENSATION
CONFIGURATION
CH anticondensation enable R/W
CH anticondensation
setpoint
CH anticondensation pump
force off
DHW anticondensation
enable
DHW anticondensation
setpoint
DHW anticondensation
pump force off
Anticondensation priority
Frost protection
anticondensation enable
R/W
U16
Maximum number of recycles due to Delta-T or inversion
limit.
R/W
U16
0=Do not limit modulation rate,
1=Limit modulation rate when approaching Delta-T
threshold
R/W
U16
Minimum toleration time for temperature inversion (0-
64800 seconds)
R/W
U16
0=Lockout,
1=Recycle&delay,
2=Recycle&delay with retry limit
R/W
U16
Delta-T limit for exchanger to outlet flow:
0=Disable Delta-T limit,
1=Enable Delta-T limit,
2=Enable Inversion detection,
3=Enable Delta-T limit and Inversion detection
R/W
U16
Temperature delta between exchanger & outlet sensors
when Delta-T limit occurs:
0°-130° (0.1°C precision)
R/W
U16
0=Disable exchanger T-rise limit,
1=Enable exchanger T-rise limit
R/W
U16
0=Lockout,
1=Recycle&delay,
2=Recycle&delay with retry limit
R/W
U16
Maximum number of recycles due to T-rise limit.
R/W
U16
Delta-T limit for inlet to exchanger flow:
0=Disable Delta-T limit,
1=Enable Delta-T limit,
2=Enable Inversion detection,
3=Enable Delta-T limit and Inversion detection
R/W
U16
Temperature delta between inlet & exchanger sensors
when Delta-T limit occurs:
0°-130° (0.1°C precision)
U16
0=Disable CH anticondensation,
1=Enable CH anticondensation
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0=Normal (no change to CH pump)
1=CH pump forced off
R/W
U16
0=Disable DHW anticondensation,
1=Enable DHW anticondensation
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0=Normal (no change to DHW pump)
1=DHW pump forced off
R/W
U16
Is anticondensation more important than (0=No, 1=Yes)?
Bit map:
15-5=Reserved (always 0)
4=Outlet high limit
3=Forced rate
2=Slow start
1=Delta-T limit
0=Stack limit
R/W
U16
0=Disable frost protection anticondensation,
1=Enable frost protection anticondensation
21
CB FALCON MODBUS COMMUNICATION
a
a
a
a