CB FALCON MODBUS COMMUNICATION
Table 4. CB Falcon Modbus register map
01F8
0504
01F9
0505
01FA
0506
01FB
0507
01FC
0508
01FD
0509
01FE-01FF 0510-0511 RESERVED
0200
0512
0201
0513
0202
0514
0203
0515
0204
0516
0205
0517
0206
0518
0207
0519
0208
0520
0209
0521
020A
0522
020B
0523
020C
0524
020D
0525
020E
0526
020F
0527
0210
0528
0211
0529
0212
0530
0213
0531
DHW STORAGE
CONFIGURATION
DHW storage enable
DHW storage time
DHW storage setpoint
DHW storage on hysteresis R/W
DHW storage off hysteresis R/W
DHW priority method
OUTDOOR RESET (ODR)
CONFIGURATION
CH ODR maximum outdoor
temperature
CH ODR minimum outdoor
temperature
CH ODR low water
temperature
CH ODR boost time
CH ODR maximum off point R/W
Lead Lag CH ODR
maximum outdoor
temperature
Lead Lag CH ODR minimum
outdoor temperature
Lead Lag CH ODR low
water temperature
Lead Lag CH ODR boost
time
Lead Lag CH ODR
maximum off point
CH ODR boost step
CH ODR boost recovery
step time
Lead Lag CH ODR boost
step
Lead Lag CH ODR boost
recovery step time
Minimum boiler water
temperature
Lead Lag CH ODR minimum
water temperature
FROST PROTECTION
CONFIGURATION
CH frost protection enable
DHW frost protection enable R/W
Outdoor frost protection
setpoint
RESERVED
R/W
U16
0=DHW storage disabled,
1=DHW storage enabled
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
-40°-130° (0.1°C precision)
U16
0°-130° (0.1°C precision)
U16
0°-130° (0.1°C precision)
R/W
U16
0=Boost DHW priority during priority time,
1=Drop DHW priority after priority time expires
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
U16
-40°-130° (0.1°C precision)
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0°-130° (0.1°C precision)
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
0°-130° (0.1°C precision)
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0=Disable CH frost protection,
1=Enable CH frost protection
U16
0=Disable DHW frost protection,
1=Enable DHW frost protection
R/W
U16
-40°-130° (0.1°C precision)