Table 4. CB Falcon Modbus register map
00E5
0229
00E6
0230
00E7
0231
00E8
0232
00E9
0233
00EA
0234
00EB
0235
00EC
0236
00ED
0237
00EE
0238
00EF
0239
00F0
0240
00F1
0241
00F2
0242
00F3
0243
00F4
0244
00F5
0245
Purge rate proving
Lightoff rate proving
Prepurge time
Pre-ignition time
Pilot flame establishing
period (PFEP)
Main flame establishing
period (MFEP)
Run stabilization time
Postpurge time
Interlock start check enable R/W
Interlock open response
Ignite failure response
Ignite failure retries
Ignite failure delay
MFEP flame failure
response
Run flame failure response
Pilot test hold
RESERVED
R/W
U16
SAFETY parameter
0=None,
1=High Fire Switch (HFS),
2=Fan speed
R/W
U16
SAFETY parameter
0=None,
1=(Low Fire Switch) LFS,
2=Fan speed,
3=Fan speed, except during ignition
R/W
U16
SAFETY parameter
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
SAFETY parameter
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
SAFETY parameter
0=None,
1=4 seconds,
2=10 seconds,
3=15 seconds,
0xFFFF=Not configured
R/W
U16
SAFETY parameter
0=None,
1=5 seconds,
2=10 seconds,
3=15 seconds,
0xFFFF=Not configured
R/W
U16
SAFETY parameter
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
SAFETY parameter
0-64800 seconds (18 hours), 0xFFFF=Not configured
U16
SAFETY parameter
0=No ILK check,
1=ILK check
R/W
U16
SAFETY parameter
0=Lockout, 1=Recycle
R/W
U16
SAFETY parameter
0=Lockout,
1=Continuous recycle,
2=Retry, recycle & hold,
3=Retry, recycle & lockout
R/W
U16
SAFETY parameter
0=None,
1=3 times,
2=5 times,
3=1 time,
0xFFFF=Not configured
R/W
U16
SAFETY parameter
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
SAFETY parameter
0=Lockout, 1=Recycle
R/W
U16
SAFETY parameter
0=Lockout, 1=Recycle
R/W