CleaverBrooks CFC-500 Operation, Service And Parts Manual page 299

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Table 4. CB Falcon Modbus register map
02F2
0754
02F3
0755
02F4
0756
02F5
0757
02F6
0758
02F7
0759
02F8
07600760
02F9-033F 0761-0831 RESERVED
0340-035F 0832-0863 RESERVED
0360-0370 0864-0880 Lockout history record 1
0371-0381 0881-0897 Lockout history record 2
0382-0392 0898-0914 Lockout history record 3
0393-03A3 0915-0931 Lockout history record 4
03A4-03B4 0932-0948 Lockout history record 5
03B5-03C5 0949-0965 Lockout history record 6
03C6-03D6 0966-0982 Lockout history record 7
03D7-03E7 0983-0999 Lockout history record 8
03E8-03F8 1000-1016 Lockout history record 9
03F9-0409 1017-1033 Lockout history record 10
Auxiliary 1 pump options 2
Auxiliary 2 pump output
Auxiliary 2 pump control
Auxiliary 2 pump start delay R/W
Auxiliary 2 pump overrun
time
Auxiliary 2 pump options 1
Auxiliary 2 pump options 2
SAFETY CONFIGURATION
LOCKOUT HISTORY
R/W
U16
Bit map:
15=Pump used for Lead Lag,
14=Pump used for local demand,
13-9=Reserved (always 0),
8=Force pump off when DHW high limit,
7=Force pump off when DHW anti-condensation,
6=Force pump off when CH anti-condensation,
5=Force pump off when DHW priority is active,
4=Force pump on when DHW frost protection,
3=Force pump on when CH frost protection,
2=Force pump on when Lead Lag slave demand,
1=Force pump on when local burner demand,
0=Force pump on when Outlet high limit
R/W
U16
0=None, 1=Pump A, 2=Pump B, 3=Pump C
R/W
U16
0=Auto, 1=On
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
Bit map:
15=Normal pump demand when auxiliary pump Z is set,
14=Normal pump demand when auxiliary pump Y is set,
13=Normal pump demand when auxiliary pump X is set,
12-7=Reserved (always 0),
6=Normal pump demand when DHW service is active,
5=Normal pump demand when CH service is active,
4=Reserved,
3=Normal pump demand when DHW demand,
2=Normal pump demand when CH demand,
1=Normal pump demand when local burner demand,
0=Local demand inhibited for faults
R/W
U16
Bit map:
15=Pump used for Lead Lag,
14=Pump used for local demand,
13-9=Reserved (always 0),
8=Force pump off when DHW high limit,
7=Force pump off when DHW anti-condensation,
6=Force pump off when CH anti-condensation,
5=Force pump off when DHW priority is active,
4=Force pump on when DHW frost protection,
3=Force pump on when CH frost protection,
2=Force pump on when Lead Lag slave demand,
1=Force pump on when local burner demand,
0=Force pump on when Outlet high limit
R
Most recent lockout. See Table 5.
R
nd
2
newest lockout. See Table 5.
R
rd
3
newest lockout. See Table 5.
R
th
4
newest lockout. See Table 5.
R
th
5
newest lockout. See Table 5.
R
th
6
newest lockout. See Table 5.
R
th
7
newest lockout. See Table 5.
R
th
8
newest lockout. See Table 5.
R
th
9
newest lockout. See Table 5.
R
th
10
newest lockout. See Table 5.
29
CB FALCON MODBUS COMMUNICATION