Nominal
Actual I.D.
Length in feet
10
20
30
40
50
60
70
80
90
100
125
150
175
200
**Fuel: Natural Gas
**Inlet Pressure: Less than 2.0 psi
**Pressure Drop: 0.50" w.c.
**Specific Gravity: 0.60
Part No. 750-263
Table 2-5: Gas Line Capacity - Schedule 40 Metallic Pipe
1"
1-1/4"
1.049"
1.380"
**Maximum Capacity in Cubic Feet of Gas per Hour (cfh)
678
1,390
466
957
374
768
320
657
284
583
257
528
237
486
220
452
207
424
195
400
173
355
157
322
144
296
134
275
Pipe Size
1-1/2"
2"
2-1/2"
1.610"
2.067"
2.469"
2,090
4,020
6,400
1,430
2,760
4,400
1,150
2,220
3,530
985
1,900
3,020
873
1,680
2,680
791
1,520
2,430
728
1,400
2,230
677
1,300
2,080
635
1,220
1,950
600
1,160
1,840
532
1,020
1,630
482
928
1,480
443
854
1,360
412
794
1,270
Section 2 — Installation
3"
4"
3.068"
4.026"
11,30
23,10
0
0
7,780
15,90
0
6,250
12,70
0
5,350
10,90
0
4,740
9,600
4,290
8,760
3,950
8,050
3,670
7,490
3,450
7,030
3,260
6,640
2,890
5,890
2,610
5,330
2,410
4,910
2,240
4,560
2-19