CleaverBrooks CFC-500 Operation, Service And Parts Manual page 277

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Table 4. CB Falcon Modbus register map
0024
0036
0025
0037
0026
0038
0027
0039
0028
0040
0029
0041
002A
0042
002B
0043
002C
0044
002D
0045
002E
0046
002F
0047
0030
0048
0031
0049
0032
0050
0033
0051
0034
0052
Annunciator first out
Annunciator hold
Sequence time
Delay time
Hold code
Burner control flags
Remote Stat
SENSOR STATUS
Outlet operation (S4=J8-10)
terminal
DHW operation (S7=J9-3)
terminal
Stack or Heat exchanger
operation (S9=J9-6)
terminal
Outlet operation sensor
(S4=J8-10) state
DHW operation sensor
(S7=J9-3) state
Outlet limit sensor (S3=J8-8)
state
Inlet sensor (S1=J8-4) state R
DHW limit sensor (S7=J9-1)
state
Stack limit sensor (S8=J9-4)
state
S5 (J8-11) sensor state
R
U16
Source for annunciator first out:
0=None or undetermined,
1=ILK,
2=PII,
11=Annunciator 1,
12=Annunciator 2,
13=Annunciator 3,
14=Annunciator 4,
15=Annunciator 5,
16=Annunciator 6,
17=Annunciator 7,
18=Annunciator 8
R
U16
Source for burner control hold condition (see Hold code):
0=None or undetermined,
1=ILK,
2=PII,
3=LCI
11=Annunciator 1,
12=Annunciator 2,
13=Annunciator 3,
14=Annunciator 4,
15=Annunciator 5,
16=Annunciator 6,
17=Annunciator 7,
18=Annunciator 8
R
U16
Running time for timed burner control operation
(seconds)
R
U16
Running delay time (seconds). Applicable when burner
control in delayed or hold state.
R
U16
Reason for burner hold (same codes as lockout, see
table 7)
R
U16
Bit map:
15-1=Reserved (always 0)
0= Flame detected
R/W
U16
0=No remote STAT demand,
1=remote STAT demand indicated
R
U16
-40°-130° (0.1°C precision)
or other (see register 610)
R
U16
-40°-130° (0.1°C precision)
R
U16
-40°-130° (0.1°C precision)
R
U16
0=None, 1=Normal, 2=Open, 3=Shorted, 4=Outside high
range, 5=Outside low range, 6=Not reliable
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
R
U16
0=None, 1=Normal, 2=Open, 3=Shorted, 4=Outside high
range, 5=Outside low range, 6=Not reliable
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
7
CB FALCON MODBUS COMMUNICATION
d
e
or other (see register 612)
e
or other (see register 613)