Field erectable flexible watertube boiler (64 pages)
Summary of Contents for CleaverBrooks CBT
Page 1
Model CBT Tubeless Vertical Boiler Operation and Maintenance Manual CBT-M — Full Modulation CBT — On/Off Operation 750-382 04/2019...
Page 2
! DANGER WARNING ! DANGER WARNING Improper installation, adjustment, service, or mainte- If the information in this manual is not followed exactly, a fire or explosion may result causing property dam- nance can cause equipment damage, personal injury, or death. Refer to the Operation and Maintenance age, personal injury or loss of life.
Page 3
CLEAVER-BROOKS Model CBT Tubeless Vertical Boiler Operation, Service, and Parts Manual Cleaver-Brooks 2019 Manual Part No. 750-382 04/2019...
Page 4
WARNING ! DANGER DO NOT OPERATE, SERVICE, OR REPAIR THIS EQUIPMENT UNLESS YOU FULLY UNDERSTAND ALL APPLI- CABLE SECTIONS OF THIS MANUAL. DO NOT ALLOW OTHERS TO OPERATE, SERVICE, OR REPAIR THIS EQUIPMENT UNLESS THEY FULLY UN- DERSTAND ALL APPLICABLE SECTIONS OF THIS MANUAL. FAILURE TO FOLLOW ALL APPLICABLE WARNINGS AND INSTRUCTIONS MAY RESULT IN SEVERE PERSONAL INJURY OR DEATH.
The Model CBT and CBT-M are UL listed for both the US and Canada. Premix technology The Model CBT-M Boiler utilizes “Premix” technology to mix both fuel and combustion air prior to entering the firing chamber. This technology provides clean, efficient combustion with very low emission levels.
Page 9
Refractory is limited to the burner dry oven and a bottom furnace target plate. FIGURE 1-2. ASME data Gases of combustion flow downward through the furnace (1), then upward through the 2nd pass (2) before exiting the flue (3). CBT heat flow FIGURE 1-2. 750-382...
Introduction 1.2 — Burner 1.2.1 — Full modulation (CBT-M) Full modulation units use a premix burner with a self-regulat- ing gas valve-venturi system, ECM variable regulating gas valve, variable speed blower, and Fecralloy metal fiber burner canister. • Full modulation is provided using the integral variable speed combustion air fan and Falcon control.
VENTURI OPTIONAL: GAS PRESSURE REGULATOR ON/OFF (CBT) FULL MODULATION (CBT-M) FIGURE 1-5. Gas train Full modulation gas train components: Single body, dual safety shutoff gas valve with integral trim regulator Low Gas Pressure Switch...
Introduction 1.4 — Controls CONTROLS ABBREVIATIONS: ALWCO - Auxiliary Low Water Cutoff HLC - High Limit Control HWA - High Water Alarm OLC - Operating Limit Control LWCO - Low Water Cutoff 1.4.1 — Full modulation controls (Optional) (Optional) (Optional) FIGURE 1-6.
Page 13
Controls • Outdoor temperature reset. • Remote firing rate or setpoint control • Setback/time-of-day setpoint • Built-in Lead-Lag control for multiple boiler systems • Warm standby-minimum temperature control 1.4.2 — On-off controls The Burner Control provides burner sequencing control and flame supervision. A switch/light panel provides functionality similar to full modulation units: indicator lights for demand, fuel valve open, alarm, low water, and (optional) high water;...
Page 14
Introduction 1.4.3 — Water level and limit controls, all boilers ALWCO probe Manual valve The pressure transmitter provides an analog steam holder pressure signal to the controller for modulated firing (full modulation units) or on/off operation. The high limit control (HLC) provides safety shutdown Steam pressure gauge when steam pressure exceeds the maximum operating range of the boiler.
1.6 — Optional equipment Certain options are available for the Model CBT Boiler; normally these will have been specified at the time of order entry. In addition, some options may have been provided (by others) that are not part of Cleaver-Brooks scope of supply.
Installation CHAPTER 2 Lifting and Moving the Boiler 2-2 Water Treatment 2-2 Boiler Room 2-4 Gas Piping 2-5 Boiler Waterside Connections 2-10 Electrical Connections 2-11 Wiring Diagrams 2-12 Warning Caution Provisions for combustion and ventilation air must The boiler must be installed such that the gas be in accordance with UL 795, Commercial- ignition system components are protected from Industrial Gas Heating Equipment, cUL, or...
Properly treated boiler water will help maximize the effectiveness and lifespan of the pressure vessel. Contact your local Cleaver-Brooks representative or water management consultant for complete information on how to prevent damage resulting from inadequate water treatment. See Table 2-1 for CBT water quality guidelines. 750-382...
Page 19
Water Treatment Important The CBT boiler requires soft water. Failure to observe this requirement can lead to dangerous operating conditions, and may result in damage to the boiler. If necessary, your Cleaver-Brooks representative can provide additional information regarding your water softening requirements.
Installation 2.3 — Boiler Room The boiler room must comply with all building codes and regulations. An adequate supply of combustion air and sufficient ventilation are required for safe operation. If the optional direct vent combustion air kit is not used, ventilation must be provided to meet applicable regulations for air supply.
*Maximum without upstream regulator A manually operated shut-off valve is provided as standard on the CBT boiler. If dirt particles are present in the gas supply, it may be necessary to install an approved gas filter. Please inquire with the local gas supply company.
Page 22
Installation If building supply gas pressure is greater than 1 psig (27.8” WC), an upstream regulator with overpressure pro- tection and proper gas venting will be required and must be piped to a safe point of discharge. For multiple boil- ler installations, a dedicated gas pressure regulator is required for each boiler to ensure consistent gas pressure at the boiler.
Page 23
Gas Piping Table 2-4. Gas line capacity - Schedule 40 metallic pipe Pipe Size Nominal 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" Actual I.D. 1.049 1.380" 1.610" 2.067" 2.469" 3.068" 4.026" Length in feet **Maximum Capacity in Cubic Feet of Gas per Hour (CFH) 1,060 1,580 3,050...
Page 24
Installation Gas header - For multiple unit installations, a single common gas header is recommended with individual takeoffs for each boiler (See Figure 2-4). Boiler gas manifold piping should be sized based on volume requirements and lengths between each boiler and the fuel main header. Tables 2-6 through 2-10 indicate the proper sizing for multiple units of equal size, placed on the factory standard center with the indicated take off size.
Page 25
DRIP LEG REQUIRED FOR ANY VERTICAL RUN OF PIPING FIGURE 2-5. Typical gas piping - Example 2 Pipe sizing for multiple unit manifolds TABLE 2- 6. CBT 10 HP boilers TABLE 2- 7. CBT 15 HP boilers # of # of...
The feedwater supply should provide sufficient pressure to meet minimum flow requirements. Cleaver-Brooks offers bottom blowdown piping and valves for CBT boilers. Optional surface blowoff is also available. A qualified boiler and piping installer should make all boiler waterside connections.
- Connect optional heat request inputs per wiring diagram - Connect pump controls per wiring diagram FIGURE 2-7. CBT wiring and cable connections Caution: The blower signal wiring must be isolated from the blower power wiring and the high voltage ignition cables.
Installation 2.7 — Wiring Diagrams Note: Wiring diagrams shown are for example only. Installations may vary. Refer to the Cleaver-Brooks wiring diagram provided with the boiler for information specific to your installation. Basic wiring diagram - full modulation 2-12 750-382...
• Category IV - A boiler which operates with a positive vent pressure and with a vent gas temperature that may cause excessive condensate production in the vent. The Model CBT will in most applications be considered a Category III boiler. In certain applications, such as with a condensing economizer, Category II or IV venting criteria may apply.
Page 33
Vent terminal location 3. The bottom of the vent terminal and the air intake shall be located at least 24 inches above grade, including normal snow line. 4. Un-insulated single-wall metal vent pipe shall not be used outside in cold climates for venting combustion gas.
Page 34
Flue and Combustion Air Venting Examine the venting system at least once a year. Check all joints and vent pipe connections for tightness, corrosion or deterioration. 3.3.1 — Venting installation tips Where to support piping: • Horizontal runs- at least every five (5) feet. •...
Horizontal through-wall venting, inside air (Category III) 3.4 — Horizontal through-wall venting, inside air (Category III) For boilers connected to gas vents or chimneys, vent installa- tions shall be in accordance with Part 7, Venting of Equipment, of the latest edition of National Fuel Gas Code, or in Canada, the latest edition of CAN/CGA-B 149.1 and.2 Installation Code for Gas Burning Appliances and Equipment, or applicable provi- sions of local building codes.
Flue and Combustion Air Venting FIGURE 3-3. Horizontal through-wall direct venting system, Category III installation 3.5 — Horizontal through-wall direct venting These installations utilize the boiler mounted blower to draw combustion air from outside and vent combustion gases to the outside. Combustion air venting can be constructed of steel, stainless steel, PVC, CPVC, or material as deemed appropri- ate for the application and per local codes.
Horizontal through-wall flue vent termination 1. The flue venting be installed with a slight upward slope of at least 1/8” per foot of horizontal run to the vent terminal. In this case, an approved condensate trap must be installed per applicable codes. 2.
Flue and Combustion Air Venting 3.7 — Vertical venting, inside combustion air (Category III) central heating Flue Vent Termination If 10’-0” (velocity cone type) or less 24” Minimum 24” Minimum FIGURE 3-4. Vertical stack with inside combustion air These installations utilize the boiler mounted blower to vent the combustion products to the outside. Combustion air is taken from inside the room and the vent is installed vertically through the roof to the outside.
Commissioning 4.1 — Full modulation boilers 4.1.1 — Operating conditions • The installation site should be as free as possible from vibration, dust, and corrosive media • The controllers should be located as far as possible from sources of electromagnetic fields, such as frequency converters or high-voltage ignition transformers •...
Page 43
Full modulation boilers CBT probe and WC levels FIGURE 4-1. 750-382...
4.1.6 — CB Falcon display/operator interface The CB Falcon display/operator interface is mounted in the boiler control panel for convenient access to all operating controls. Note: CBT boilers will be equipped with the 833-05105 System Display. For more information see Appendix B. 750-382...
Page 46
Commissioning Home page Apply power to the boiler. The Home page will appear on the CB Falcon display. FIGURE 4-5. Home Page If the screen does not display properly when the unit is powered up: • Verify that the controller is receiving power. •...
Page 47
Full modulation boilers Note: The “Home” icon at the upper left of the display screen always returns to the Home Page. The “Back” icon at the upper right displays the previous screen. The camera icon will take a snapshot of the currently displayed screen. Up to 16 snapshots can be saved and loaded to a USB device.
Page 48
Commissioning Status page FIGURE 4-8. The Demand display will show one of the following: Burner enable off Off (burner switch on but no demand) Steam Burner state shows the currently active step in the burner operating sequence. The central portion of the display can be toggled between the following: Pumps shows the status of the pump/auxiliary relay contacts Modulation shows fan speed RPM settings for Demand, Limited, and Override rates Setpoints shows the ON, Modulation, and OFF setpoints.
Full modulation boilers Operation page FIGURE 4-9. Operation page From the Operation Page page the user can change setpoints, manually control the boiler’s firing rate, manually turn pumps on, and view annunciation information. If a password is required to change any of the settings on this page, the user can press the Login button to enter the password.
4.1.8 — Controller configuration The CB Falcon controller should be factory configured for the specific CBT boiler model. Prior to starting the boiler, verify that the factory default settings are correct for your application. Please refer to CB default settings, Table 4-1, and make any changes at this time if needed.
Page 51
Full modulation boilers TABLE 4- 1. CB Falcon factory parameter settings - Model CBT-M (Continued) Parameter Group Parameter Name Access Min. Default Setting Max. Parameter Units Installation Modbus Range Range Setting Register (dec) Steam Configuration Steam modulation Service C:Modulation from...
Page 52
Commissioning TABLE 4- 1. CB Falcon factory parameter settings - Model CBT-M (Continued) Parameter Group Parameter Name Access Min. Default Setting Max. Parameter Units Installation Modbus Range Range Setting Register (dec) Pump Configuration Auxiliary 2 pump Service 0m 0s mmm ss...
Page 53
Full modulation boilers TABLE 4- 1. CB Falcon factory parameter settings - Model CBT-M (Continued) Parameter Group Parameter Name Access Min. Default Setting Max. Parameter Units Installation Modbus Range Range Setting Register (dec) Annunciation Annunciator 6 long LOW GAS Configuration...
Page 54
Commissioning TABLE 4- 1. CB Falcon factory parameter settings - Model CBT-M (Continued) Parameter Group Parameter Name Access Min. Default Setting Max. Parameter Units Installation Modbus Range Range Setting Register (dec) Burner Control Lightoff rate Service 1000rp 2000rpm 3000rpm Ignition...
Page 55
Full modulation boilers TABLE 4- 1. CB Falcon factory parameter settings - Model CBT-M (Continued) Parameter Group Parameter Name Access Min. Default Setting Max. Parameter Units Installation Modbus Range Range Setting Register (dec) Lead Lag Master Lead lag D gain...
Page 56
Commissioning TABLE 4- 1. CB Falcon factory parameter settings - Model CBT-M (Continued) Parameter Group Parameter Name Access Min. Default Setting Max. Parameter Units Installation Modbus Range Range Setting Register (dec) Lead Lag Slave Slave mode Service Equalize runtime Configuration...
4.1.10 — Burner sequence In addition to providing modulation control, the CB Falcon is responsible for flame supervision and burner sequencing. The CBT boiler uses direct spark ignition (no pilot) to light the main flame. Flame FIGURE 4-12. Program module sensing is accomplished using an ultraviolet (UV) flame detector.
Model CBT gas train. Note: The flange. Do not use the leak test cocks to measure gas maximum rated inlet pressure to the CBT gas train is 1 psig (28" WC). pressure. An upstream regulator and overpressure protection are required if building supply gas pressure is greater than 1 psig.
4. The burner and its gas connection must be leak tested before placing the boiler into operation. 5. Gas Pressure Regulator - Using the adjusting screw on the main gas regulator, adjust the inlet pressure to the recommended levels in Table 4-3. TABLE 4- 3. CBT Gas Pressure Requirements CBT Size Natural Gas LP Gas Min (“WC)
Commissioning 4.1.15 — Operation check: gas valve, gas pressure switches, and combustion air proving switch Before initial firing of the burner, the gas valve, Low Gas Pressure Switch (LGPS), High Gas Pressure Switch (HGPS), and Combustion Air Proving Switch (CAPS) should be checked for proper operation. •...
ALWCO 1. To check the ALWCO, drain the boiler (refer to Chapter 5, Section 5.2 - Blowdown). 2. Observe the ALWCO control board in the CBT electrical panel. When the ALWCO level is reached, the LED indicator should go out.
4.1.19 — Setting Combustion Note: A Combustion Analyzer is required to properly set-up the Model CBT burner. Do not attempt to fire and adjust the burner without this equipment. Note: Ensure boiler is filled with water prior to burner startup.
Page 63
Full modulation boilers Manual Modulation - use the procedure below to change the burner firing rate manually. 1. On the CB Falcon Operation screen, press 2. A numeric keypad will appear, the Firing rate display. showing the current firing rate and operating mode.* 3.
Commissioning To set combustion: FIGURE 4-18. Operation screen 1. Check inlet gas pressure and reset low gas pressure switch. 2. At Operation screen set firing rate to low fire. Review burner sequence before proceeding. 3. Turn Demand switch to LOCAL. 4.
On/off boilers The OLC and HLC can be tested while the boiler is producing steam by adjusting the switch setting downward. A lockout should result when the switch setting is at or just below the current steam pressure. Readjust each switch (and reset HLC) after testing. 4.2 —...
Commissioning 5. All valves in the piping leading to or from the system must be closed to prevent cleaning solution from getting into the system. 6. Fill the boiler vessel with enough clean water to cover the furnace. Add the cleaning solution, then fill to the top.
The Time-of-Day (TOD), or setback, set point is an alternative set point that is enabled when a remote contact connected to terminals J10-2 & J10-3 is closed (Refer to Figure 2-8 CBT Wiring Diagram). When the circuit is open, the boiler control reverts back to the normal set point. The TOD set point can be adjusted at either the Operation page or under the Steam Configuration parameter group.
Page 68
Commissioning Remote enable and remote 4-20mA input Remote enable and Remote 4-20mA input allow the boiler to be sequenced and/or controlled from a separate boiler room controller or building management system. The 3-position Demand switch at the front of the control panel determines whether the boiler is off, in local, or under remote control.
Maintenance 5.1 — General A well-planned maintenance program will help avoid unnecessary downtime or costly repairs, and will promote safety and aid boiler inspectors. It is recommended that a boiler room log or record be maintained. Recording of daily, weekly, monthly, and yearly maintenance activities will help to obtain economical and lengthy service from the equipment.
Water column blowdown Caution • Never pump the quick-opening valve to blow down the boiler. Such action could cause water hammer and damage the piping and valves. It could also cause personal injury. • Never leave an open blowdown valve unattended. •...
Page 72
Maintenance Open Open Closed 1. Open Water Column blowdown valve (5 to 3. Close upper gauge glass isolation valve. 10 sec.) to discharge water from WC. 4. Open gauge glass blowdown valve to 2. Close WC blowdown valve. discharge water from gauge glass. 8.
Fireside cleaning procedure/disassembly Close the valves when replacing the glass. Slip a packing nut, packing washer, and packing ring onto each end of the glass. Insert one end of the glass into the upper gauge valve body far enough to allow the lower end to be dropped into the lower body.
Page 74
Maintenance DRY OVEN BURNER CAN GASKET BURNER CAN SIGHT GASKET GLASS BURNER CANISTER ADAPTER PLATE ADAPTER PLATE GASKET BLOWER UNIT UV SCANNER IGNITION ELECTRODE VENTURI FIGURE 5-3. Burner assembly - full modulation SPRING PIN ELECTRODE ORIFICE PLATE LOCK WASHER STANDOFF BAFFLE WELDMENT LOCK WASHER SCREW...
Ignition electrode 5.5 — Ignition electrode 5.5.1 — Full modulation burners Caution The dimensions on the Ignition Electrode are not easily adjustable. Bending the rods can cause damage to the insulating material. In addition, a bent electrode will have a tendency to return to its original shape when heated. If the electrode is out of specification, replacement is generally recommended.
Maintenance 5.7 — Waterside inspection/cleaning Waterside inspection frequency may depend upon the local jurisdiction and inspector but it is recommended that a waterside inspection take place 2-3 months after initial startup. C-B further recommends to semiannually remove all handhole covers and thoroughly clean the water side cavity and bottom of the boiler.
Safety valve 5.8 — Safety valve The safety valve is an important safety device and deserves attention accordingly. Follow the recommendations of your boiler inspector regarding valve inspection and testing. The frequency of testing, either by use of the lifting lever or by raising the steam pressure, should be based on the recommendation of your boiler inspector and/or the valve manufacturer, and should be in accordance with Sections VI and VII of the ASME Boiler and Pressure Vessel Code.
Page 80
Maintenance The alert (or lockout) list will appear, showing date and time for each item. Pressing an individual item in the list will display additional information. Diagnostic information available for lockouts includes annunciator status, states of system inputs, and steam pressure at time of lockout. The Falcon display touch-screen interface is a valuable tool to help identify and resolve conditions that prevent normal and safe operation of the boiler.
Page 81
Troubleshooting TABLE 5- 1. CBT troubleshooting Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures Boiler will not start -- A. Hold 63 LCI Off A.1. Touch Screen Check demand state Turn Demand switch to no lockout or alarm “Demand” status is in...
Page 82
Maintenance Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures Check blowdown valve All blowdown valves positions. should be closed during operation, except during active blowdown proce- dures. Close any blow- down valves that may be open. B.2. Feed Water (FW) Check for power to FW If no power present -- pump is not running,...
Page 83
Troubleshooting Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures Inspect high-temp Tighten jam nuts on wire-to-probe connec- any loose probe con- tions in boiler water nections. column connection box (Warrick) If slight corrosion pres- ent, remove terminal connection, clean crimp-on ring termi- nal, re-crimp, and replace with copper...
Page 84
Maintenance Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures C. Demand: Steam C.1. Steam pressure is Note Modulation set Change steam Set Burner state: Standby greater than Falcon ON point, ON and OFF Point, On hysteresis, (normal) point (SP - ON hystere- points on status screen and Off hysteresis sis)
Page 85
Troubleshooting Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures Check Auxiliary Low If LED remains off after Water Cut-off (ALWCO) reset and LWCO control LED inside con- “LLCO” LED is ON, trol panel. Also observe perform water column primary LWCO control and boiler bottom “LLCO”...
Page 86
Maintenance Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures H. Lockout 67 ILK OFF H.1. Insufficient gas Check gas supply pres- Confirm gas shut-off LOW GAS PRESSURE supply pressure or gas sure at boiler gas valve valve is open. Increase valve closed inlet during trial for gas supply to boiler...
Page 87
Troubleshooting Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures J.2. Combustion Air Visually inspect blower Check that blower Blower does not run or cable/harness connec- cable/harnesses are does not run to purge tions. secure on both ends: speed (4000 RPM) 3-conductor power cable to blower power circuit and 4-conductor...
Page 88
Maintenance Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures Check if blower is turn- Resolve draft condi- ing when not on. tion (e.g. adjust stack damper) to near neu- tral (0" w.c.) K.2. Blower running Check Firing rate and If Firing rate indicates when boiler is off Fan speed on Falcon...
Page 89
Troubleshooting Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures L.4. Gas supply restric- Monitor gas supply If significant fluctations tion -- improperly sized pressure at boiler gas in gas pressure (e.g. 5" high pressure regulator, valve inlet during trial to 10"...
Page 90
Maintenance Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures L.10. Burner canister Check for flame signal inspect burner/clean clogged surface. Replace burner canister if clogged or damaged. Clear Lockout and try again L.11. No or poor flame Check for flame sig- If flame observed, signal (less than 1 nal;...
Page 91
Troubleshooting Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures M.3. Flame Rod (Ion- Check flame signal and Increase the gap ization Electrode) inspect flame rod posi- between the flame rod grounding itself tion. tip to the burner canis- ter surface. Replace flame rod if damaged.
Page 92
Maintenance Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures O. Lockout 173 Pilot O.1. Loose wire or neu- Check fuel valve wir- Correct/secure any relay feedback error tral in fuel valve circuit ing from control panel loose wire connections to gas valve connection in fuel valve circuit.
Page 93
Troubleshooting Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures Q.3. Low fire (Mini- Observe if Lockout Increase Minimum mum modulation occurs at lower firing modulation speed by speed) too low rate. Compare Mini- 100-300 RPM as mum modulation needed. parameter setting to Manual commission- ing recommendation.
Page 94
Maintenance Problem Display Message Possible Cause/Symp- Diagnostic Check Corrective Measures S.2. Anti-short cycle Check anti-short cycle Reduce ant-short cycle time is too long time time parameter; set to 0 to disable this func- tion. Anti-short cycle is located in the "Steam Configuration"...
Display diagnostics 5.10 — Display diagnostics The CB Falcon display/interface provides diagnostic features under the Setup menu. To access display diagnostics, beginning on the Home screen, press <Setup>, then <Display Diagnostics> If the touch screen is not working properly, it may require re-calibration. Go to Display Diagnostics as above and press <Calibrate Screen>.
Page 97
Parts CHAPTER 6 Recommended spare parts list 6-2 Safety valves 6-3 Control panel 6-4 Burner assembly 6-6 Water Column 6-12 Feedwater piping 6-13 Gas train 6-14 Direct vent kits 6-15 750-382...
Parts 6.1 — Recommended spare parts list PART NUMBER DESCRIPTION 10-15 HP 20-25 HP 30 HP Falcon controller, steam 833-03578 Falcon Display 833-05105 Power Supply, 12VDC 832-02179 Gasket, Adapter Plate To Blower 380-01037 Gasket, Burner Canister (2) 380-01136 380-00902 380-01169 Burner Canister 380-01134 380-00900...
Safety valves 6.2 — Safety valves SAFETY VALVES CBT BOILERS SAFETY BOILER PRESSURE PART NO. SIZE 940-04991- x 1.50 940-04991- x 1.50 940-04991- x1.50 940-04992- x 2.00 940-04992- x 2.00 940-07988- x 1.25 940-07988- x 1.25 940-07988- x 1.25 940-02268- x 2.00...
Direct vent kits 6.8 — Direct vent kits CBT SIZE KIT NO DESCRIPTION 10-20 HP 880-04494-000 4" DIRECT VENT KIT 880-04494-000 4" DIRECT VENT KIT 25 HP 880-02737-000 6" DIRECT VENT KIT 880-02737-000 6" DIRECT VENT KIT 30 HP 6-15...