CB FALCON MODBUS COMMUNICATION
Table 4. CB Falcon Modbus register map
0035
0053
0036
0054
0037
0055
0038
0056
0039
0057
003A
0058
003B
0059
003C
0060
003D-003F 0061-0063 RESERVED
0040
0064
0041
0065
0042
0066
0043
0067
0044
0068
0045
0069
0046
0070
0047
0071
0048
0072
0049
0073
004A
0074
004B-004F 0075-0079 RESERVED
4-20mA remote control
input(S2=J8-6) state
Pressure sensor (S1=J8-4)
state
Stack operation or Heat
exchanger sensor (S9=J9-6)
state
DEMAND AND
MODULATION STATUS
Active rate limiter
Limited rate
Active rate override
Override rate
Demand rate
CENTRAL HEATING (CH)
STATUS
CH status
CH setpoint source
CH heat demand
CH burner demand
CH requested rate
CH frost heat demand
CH frost burner demand
Active CH on hysteresis
Active CH off hysteresis
Active CH pressure on
hysteresis
Active CH pressure off
hysteresis
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
R
U16
0=None,
1=Outlet high limit,
2=Delta T limit,
3=Stack limit,
4=Slow start limit,
5=Anti-condensation,
6=Minimum modulation,
7=Forced rate,
8= IAS is open
R
U16
c
RPM or %
R
U16
0=None,
1=Burner control default,
2=Burner control,
3=Manual firing rate,
4=Manual firing rate off,
5=Fan on during off cycle
R
U16
c
RPM or %
R
U16
c
RPM or %
R
U16
0=Unknown,
1=Disabled,
2=Normal,
3=Suspended
R
U16
0=Unknown,
1=Normal setpoint,
2=TOD setpoint,
3=Outdoor reset,
4=Remote control
R
U16
0=Off,
1=On
R
U16
0=Off,
1=On
R
U16
c
RPM or %
R
U16
0=Off,
1=On
R
U16
0=Off,
1=On
R
U16
0°-130° (0.1°C precision)
R
U16
0°-130° (0.1°C precision)
R
U16
0-150psi (0.1psi precision)
R
U16
0-150psi (0.1psi precision)
8