CB FALCON MODBUS COMMUNICATION
Table 8. Falcon lockout and hold codes
Code
Description
0
None
1
Unconfigured safety data
2
Waiting for safety data verification
3
Internal fault: Hardware fault
4
Internal fault: Safety Relay key
feedback error
5
Internal fault: Unstable power (DCDC)
output
6
Internal fault: Invalid processor clock
7
Internal fault: Safety relay drive error
8
Internal fault: Zero crossing not detected Hold
9
Internal fault: Flame bias out of range
10
Internal fault: Invalid Burner control state Lockout
11
Internal fault: Invalid Burner control
state flag
12
Internal fault: Safety relay drive cap short Hold
13
Internal fault: PII shorted to ILK
14
Internal fault: HFS shorted to LCI
15
Internal fault: Safety relay test failed
due to feedback ON
16
Internal fault: Safety relay test failed
due to safety relay OFF
17
Internal fault: Safety relay test failed
due to safety relay not OFF
18
Internal fault: Safety relay test failed
due to feedback not ON
19
Internal fault: Safety RAM write
20
Internal fault: Flame ripple and overflow Hold
21
Internal fault: Flame number of
sample mismatch
22
Internal fault: Flame bias out of range
23
Internal fault: Bias changed since
heating cycle starts
24
Internal fault: Spark voltage stuck low
or high
25
Internal fault: Spark voltage changed too
much during flame sensing time
26
Internal fault: Static flame ripple
27
Internal fault: Flame rod shorted to
ground detected
28
Internal fault: A/D linearity test fails
29
Internal fault: Flame bias cannot be set
in range
30
Internal fault: Flame bias shorted
to adjacent pin
31
Internal fault: SLO electronics
unknown error
32
Internal fault: Safety Key 0
Table 8. Falcon lockout and hold codes
33
Internal fault: Safety Key 1
Note
34
Internal fault: Safety Key 2
No lockout/
35
Internal fault: Safety Key 3
hold
36
Internal fault: Safety Key 4
Lockout
37
Internal fault: Safety Key 5
Lockout
38
Internal fault: Safety Key 6
Hold
39
Internal fault: Safety Key 7
Hold
40
Internal fault: Safety Key 8
41
Internal fault: Safety Key 9
Hold
42
Internal fault: Safety Key 10
Hold
43
Internal fault: Safety Key 11
Hold
44
Internal fault: Safety Key 12
45
Internal fault: Safety Key 13
Hold
46
Internal fault: Safety Key 14
47
Flame rod to ground leakage
Lockout
48
Static flame (not flickering)
49
24VAC voltage low/high
50
Modulation fault
Hold/
51
Pump fault
Lockout
52
Motor tachometer fault
Hold/
Lockout
53
AC inputs phase reversed
Lockout
54
Safety GVT model ID doesn't
match application's model ID
Lockout
55
Application configuration data block CRC
errors
Lockout
56-57
RESERVED
58
Internal fault: HFS shorted to IAS
Lockout
59
Internal fault: Mux pin shorted
60
Internal fault: HFS shorted to LFS
Lockout
61
Anti short cycle
62
Fan speed not proved
Hold
63
LCI OFF
64
PII OFF
Hold
Hold
65
Interrupted Airflow Switch OFF
Hold
66
Interrupted Airflow Switch ON
Hold
67
ILK OFF
Hold
68
ILK ON
Hold
69
Pilot test hold
Hold
70
Wait for leakage test completion
Hold
71-77
RESERVED
78
Demand lost in run
Hold
79
Outlet high limit
Hold
80
DHW high limit
Lockout
32
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Hold
Hold
Hold
Hold
Hold
Hold
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Hold
Hold
Hold
Hold/
Lockout
Hold/
Lockout
Hold/
Lockout
Hold/
Lockout
Hold/
Lockout
Hold
Hold
Hold
Hold/
Lockout
Hold/
Lockout