Table 4. CB Falcon Modbus register map
0130
0304
0131
0305
0132-013E 0306-0318 Annunciator 1 configuration R/W
013F-014B 0319-0331 Annunciator 2 configuration R/W
014C-0158 0332-0344 Annunciator 3 configuration R/W
0159-0165 0345-0357 Annunciator 4 configuration R/W
0166-0172 0358-0370 Annunciator 5 configuration R/W
0173-017F 0371-0383 Annunciator 6 configuration R/W
0180-018C 0384-0396 Annunciator 7 configuration R/W
018D-0199 0397-0409 Annunciator 8 configuration R/W
019A-01A5 0410-0421 PII configuration
01A6-01B1 0422-0433 LCI configuration
01B2-01BD 0434-0445 ILK configuration
01BE-01BF 0446-0447 RESERVED
01C0
0448
01C1
0449
01C2
0450
01C3
0451
01C4
0452
01C5
0453
01C6
0454
01C7
0455
01C8
0456
01C9
0457
01CA
0458
01CB
0459
01CC
0460
01CD
0461
ANNUNCIATION
CONFIGURATION
Annunciation enable
Annunciator mode
DHW CONFIGURATION
DHW enable
DHW demand switch
DHW priority vs CH
DHW priority vs LL
DHW priority time
DHW setpoint
DHW time of day setpoint
DHW on hysteresis
DHW off hysteresis
DHW P-gain
DHW I-gain
DHW D-gain
DHW hysteresis step time
DHW modulation sensor
R/W
U16
0=Annunciation disabled,
1=Annunciation enabled
R/W
U16
0=Fixed,
1=Programmable
See table 6.
See table 6.
See table 6.
See table 6.
See table 6.
See table 6.
See table 6.
See table 6.
R/W
See table 7.
R/W
See table 7.
R/W
See table 7.
R/W
U16
0=DHW disabled,
1=DHW enabled
R/W
U16
Source of DHW demand:
0= Modulation sensor only,
1=EnviraCOM DHW request,
2=DHW switch,
3=Unused,
4=STAT terminal,
5=Reserved,
6=Modbus STAT,
7=Auto: S6 or EnviraCOM DHW request,
8=Auto: S6 or sensor only,
9=Plate heat exchanger
R/W
U16
0=CH > DHW,
1=DHW > CH
R/W
U16
0=LL > DHW,
1=DHW > LL
R/W
U16
0=No DHW priority time,
>0=DHW priority time (seconds)
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
-40°-130° (0.1°C precision)
switch is on.
R/W
U16
0°-130° (0.1°C precision)
R/W
U16
0°-130° (0.1°C precision)
R/W
U16
0-1000
R/W
U16
0-1000
R/W
U16
0-1000
R/W
U16
0-64800 seconds (0=Disable hysteresis stepping)
R/W
U16
Sensor used for DHW modulation:
0=DHW sensor,
1=Outlet sensor,
2=Inlet sensor,
3=Modbus,
4=Auto: DHW or Inlet sensor,
5=Auto: DHW or Outlet sensor
19
CB FALCON MODBUS COMMUNICATION
a
a
Setpoint when Time Of Day
a
a