CleaverBrooks CFC-500 Operation, Service And Parts Manual page 228

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

CB FALCON
Table 48. Example of a Completed Device Parameter Worksheet. (Continued)
Parameter Name
Stack limit delay
Delta-T enable
Delta-T degrees
Delta-T response
Delta-T delay
DHW high limit enable
DHW high limit setpoint
DHW high limit response
CH slow start enable
DHW slow start enable
Slow start ramp
Slow start setpoint
CH anticondensation enable Read Only
CH anticondensation
setpoint
CH anticondensation pump
Force Off
DHW anticondensation
enable
DHW anticondensation
setpoint
DHW anticondensation pump
force off
Anticondensation > Outlet
limit
Anticondensation > Delta-T
Anticondensation > Stack
limit
Anticondensation > Slow
start
Anticondensation > Forced
rate
CH ODR max outdoor
temperature
CH ODR min outdoor
temperature
CH ODR min water
temperature
CH frost protection enable
DHW frost protection enable Read Only
Outdoor frost protection
setpoint
750-265
Customer
Choice - Hidden,
Read Only or
Password
protected
Minimum Range
Read Only
Read Only
Read Only
Read Only
[ A #b C #d ]
Read Only
Read Only
Read Only
32°F 0°C
Read Only
[ A B #c D ]
Read Only
Read Only
Read Only
Read Only
0°F -18°C
Read Only
32°F 0°C
Read Only
Read Only
Read Only
32°F 0°C
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
32°F 0°C
Read Only
Read Only
Default Setting
5m 0s
Disabled
30°F 17°C
A:Lockout
5m 0s
Enabled
150°F 66°C
240°F 116°C
D:Suspend DHW
Disabled
Disabled
10%
20°F -7°C
180°F 82°C
Disabled
135°F 57°C
240°F 116°C
Disabled
Disabled
135°F 57°C
240°F 116°C
Disabled
No/False/Off
No/False/Off
No/False/Off
Yes/True/On
Yes/True/On
80°F 27°C
0°F -18°C
50°F 10°C
240°F 116°C
Disabled
Disabled
32°F 0°C
104
Maximum Range Parameter Units
mmm:ss
mmm:ss
% | RPM per
minute