CleaverBrooks CFC-500 Operation, Service And Parts Manual page 311

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Table 10. Falcon alert codes
572
Heat exchanger high limit was exceeded
573
Heat exchanger high limit wasn't allowed due to
stack limit setting
574
Heat exchanger high limit wasn't allowed due to
stack connector setting
575
Heat exchanger high limit delay was not configured
for recycle response
576
CH pump output was invalid
577
DHW pump output was invalid
578
Boiler pump output was invalid
579
Auxiliary pump output was invalid
580
System pump output was invalid
581
Mix pump output was invalid
582-589 RESERVED
590
DHW plate preheat setpoint was invalid
591
DHW plate preheat ON hysteresis was invalid
592
DHW plate preheat OFF hysteresis was invalid
593
Tap detect degrees was out of range
594
Tap detect ON hysteresis was invalid
595
Inlet - DHW tap stop degrees was out of range
596
Outlet - Inlet tap stop degrees was out of range
Burner control states are provided in Table 11.
CB FALCON MODBUS COMMUNICATION
Table 11. Burner control states
State
0
Initiate
1
Standby Delay
2
Standby
3
Safe Startup
4
Prepurge - Drive to Purge Rate
5
Prepurge – Measured Purge Time
6
Prepurge – Drive to Lightoff Rate
7
Preignition Test
8
Preignition Time
9
Pilot Flame Establishing Period
10
Main Flame Establishing Period
11
Direct Burner Ignition
12
Run
13
Postpurge
14
Lockout
15
Prepurge (Fulton pulse)
16
Ignition (Fulton pulse)
17
Combustion Pressure Establish (Fulton pulse)
18
Combustion Pressure Stabilization (Fulton pulse)
19
Main Flame Stabilization (Fulton pulse)
255
Safety Processor Offline
The Falcon pump status codes are contained in the following
two tables. Table 12 is for older units (application build less
than 1600) and Table 13 is for newer units (application build
1600 or higher).