Parameter
Temperature Units
F, C
This parameter determines whether the temperature is represented in units of Fahrenheit or Celsius
degrees.
Anti short cycle time
mm:ss
Whenever the burner is turned off due to no demand, the anti short cycle timer is started and the
burner remains in a Standby Delay condition waiting for this time to expire. The anti short cycle time
does not apply, however, to recycle events such as loss of airflow or flame, it applies only to loss of
demand.
The anti short cycle time always inhibits a CH or LL demand. However, if a DHW demand occurs
then its priority is checked. If it has the highest priority because of either:
• a non-zero value in the DHW priority timer (which is loaded using the DHW priority time
• due to the setting in both: DHW priority vs LL (if Lead Lag Master enable is enabled) AND DHW
• then the anti short cycle delay is ignored and the DHW demand is served.
Burner name
text
The Burner Name is a text parameter stored in the Falcon to identify the burner.
OEM ID
text
The OEM ID is a text parameter stored in the Falcon intended for use by an OEM to record
identification information related to the OEM's configuration and setup of the Falcon.
Installation Data
text
The Installation Data is a text parameter stored in the Falcon. It is intended for use by the installer to
record identification information about how the Falcon was set up at the installation time.
Table 7. General Configuration Settings.
parameter)
priority vs CH (if CH enable is enabled)
Comment
21
CB FALCON