CleaverBrooks CFC-500 Operation, Service And Parts Manual page 81

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Parameter Group
Parameter Name
Fan Configuration
Fan speed up ramp
Fan Configuration
Fan speed down ramp
Fan Configuration
Fan gain up
Fan Configuration
Fan gain down
Fan Configuration
Fan min. duty cycle
High Limits
Outlet high limit enable
High Limits
Outlet high limit setpoint
High Limits
Outlet high limit response
High Limits
DHW high limit enable
High Limits
DHW high limit setpoint
High Limits
DHW high limit response
Stack Limit
Stack limit enable
Stack Limit
Stack limit setpoint
Stack Limit
Stack limit response
Stack Limit
Stack limit delay
Delta-T enable - Inlet to
Delta T Limits
outlet flow
Delta-T degrees - Inlet to
Delta T Limits
outlet flow
Delta T Limits
Delta-T response
Delta T Limits
Delta-T delay
Delta T Limits
Delta-T retry limit
Delta T Limits
Delta-T rate limit enable
Delta T Limits
Delta-T inverse limit time
Delta-T inverse limit
Delta T Limits
response
Delta-T enable - Exchanger
Delta T Limits
to outlet flow
Delta-T degrees - Exchanger
Delta T Limits
to outlet flow
Delta-T enable - Inlet to
Delta T Limits
Exchanger flow
Delta-T degrees - Inlet to
Delta T Limits
Exchanger flow
T-rise Limit
Outlet T-rise enable
T-rise Limit
T-rise degrees
T-rise Limit
T-rise delay
T-rise Limit
Exchanger T-rise enable
T-rise Limit
T-rise response
T-rise Limit
T-rise retry limit
Heat exchanger high limit
Heat Exchanger High Limit
enable
Heat exchanger high limit
Heat Exchanger High Limit
setpoint
Heat exchanger high limit
Heat Exchanger High Limit
response
Heat exchanger high limit
Heat Exchanger High Limit
delay
Heat Exchanger High Limit
Heat exchanger retry limit
Plate HX Preheat
Plate preheat delay after tap
Plate HX Preheat
Plate preheat setpoint
Plate preheat on recognition
Plate HX Preheat
time
Plate HX Preheat
Plate preheat ON hysteresis
Part No. 750-263
Table 4-1 CFC default parameter settings
Min.
Access*
Range
Service
Service
Service
Service
Service
Read Only
Service
32
Read Only
Service
Service
32
Service
Service
Service
32
Service
Service
Service
Service
14
Service
Service
Service
Service
Service
Service
Service
Service
14
Service
Service
14
Service
Service
Service
Service
Service
Service
Service
Service
32
Service
Service
Service
Service
Service
Service
Service
Max.
Default Setting
Range
0
0
1000
0
0
1000
0
30
100
0
30
100
5
10
100
Enabled
180
210
Lockout
Disabled
No value
210
Recycle & hold
Disabled
250
266
Lockout
0
300
900
Enabled ΔT and
inversion detect
50
160
Recycle & Delay w/
retry limit
0
5
480
0
3
100
Enabled
5
30
Recycle & Delay w/
retry limit
Disabled
50
160
Disabled
50
160
Disabled
10
5
Disabled
Recycle & Delay w/
retry limit
10
Disabled
200
266
Recycle & Delay w/
retry limit
0
5
900
Lockout
90
200
10
5
Section 4 — CFC Commissioning
Parameter
Units
Installation Setting
RPM/sec
RPM/sec
%
°F
°F
°F
seconds
°F
minutes
retries (b4
lockout)
minutes
°F
°F
not used
°F
not used
minutes
notused
not used
notused
not used
not used
°F
not used
notused
minutes
not used
not used
seconds
not used
°F
not used
seconds
not used
°F
not used
Modbus
Register
(dec)
0260
0261
0262
0263
0264
0484
0464
0465
0474
0475
0476
0466
0467
0468
0469
0470
0471
0472
0473
0485
0486
0487
0488
0489
0490
0494
0495
0481
0482
0483
0491
0492
0493
0592
0593
0594
0595
0596
0688
0689
0690
0691
4-11