CleaverBrooks CFC-500 Operation, Service And Parts Manual page 297

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Table 4. CB Falcon Modbus register map
0272
0626
0273
0627
0274
0628
0275
0629
0276-02AF 0630-0687 RESERVED
02B0
0688
02B1
0689
02B2
0690
02B3
0691
02B4
0692
02B5
0693
02B6
0694
02B7
0695
02B8
0696
02B9
0697
02BA
0698
02BB
0699
02BC-02BF 0700-0703 RESERVED
02C0
0704
02C1
0705
02C2
0706
02C3-02C6 0707-0710 RESERVED
02C7
0711
02C8
0712
Outdoor temperature source R/W
Warm weather shutdown
enable
Warm weather shutdown
setpoint
Use STAT with EnviraCOM
remote stat
DHW PLATE HEAT
EXCHANGER
CONFIGURATION
Plate preheat delay after tap R/W
Plate preheat setpoint
Plate preheat on recognition
time
Plate preheat on hysteresis R/W
Plate preheat off hysteresis R/W
Plate preheat minimum on
time
Tap detect degrees
Tap detect on hysteresis
Tap detect on recognition
time
Tap stop DHW-Inlet degrees R/W
Tap stop Outlet-Inlet
degrees
Tap detect minimum on time R/W
EXTENDED LEAD LAG
CONFIGURATION
Lead Lag DHW demand
switch
Lead Lag DHW setpoint
Lead Lag DHW priority vs.
CH
Warm weather shutdown
enable
Warm weather shutdown
setpoint
U16
0=Unconfigured,
1=S5 connector,
2=S10 connector,
3=Modbus,
4=EnviraCOM sensor
R/W
U16
0=Disable,
1=Enable
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0=Disable,
1=Enable
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
U16
0°-130° (0.1°C precision)
U16
0°-130° (0.1°C precision)
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
Rate of temperature drop in DHW sensor when tap
detection is declared:
0°-130° / second (0.1°C precision)
R/W
U16
0°-130° (0.1°C precision)
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
U16
Temperature delta between DHW & inlet sensors when
tap demand is stopped (drops below this limit):
0°-130° (0.1°C precision)
R/W
U16
Temperature delta between outlet & inlet sensors when
tap demand is stopped (drops below this limit):
0°-130° (0.1°C precision)
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
0=DHW loop is disabled,
1=STAT terminal,
2=Reserved,
3=EnviraCOM DHW request,
4=Unused
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0=CH > DHW,
1=DHW > CH
R/W
U16
0=Disable,
1=Enable
R/W
U16
-40°-130° (0.1°C precision)
27
CB FALCON MODBUS COMMUNICATION
a
a
a
a
a
a
a
a
a
a