Connector Term.
E1
Spark
8kV minimum open circuit voltage; 2.8mJ
at the igniter
Plug In Module (PM7910)
1
VCC
2
CSO
3
CS1
4
SDA
5
SCL
6
GND
Flame +
FS +
Testpoint for Flame signal. 0 to 10 VDC
Flame -
FS -
Testpoint for Flame signal - Ground
reference.
a
Not used by Falcon steam control
Combination #
Ignition
1
No Load
2
No Load
3
4.5A Ignition
4
4.5A Ignition
5
4.5A Ignition
a
For Direct Burner Ignition (DBI) the main valve gets connected to J5 terminal 2.
Table 3. Falcon Contact. (Continued)
Function
b
For single sensor 10K or 12K connect to TEMP A Terminals.
Table 4. Valve Load Ratings.
Pilot Valve
180 VA Ignition + motorized valves with 660
VA inrush, 360 VA opening, 250 VA holding
50VA Pilot Duty + 4.5A Ignition
65VA pilot duty + motorized valves with 3850
VA inrush, 700 VA opening, 250 VA holding
2A Pilot Duty
2A Pilot Duty
Description and Rating (All Models)
a
65VA pilot duty + motorized valves with 3850
VA inrush, 700 VA opening, 250 VA holding
65VA pilot duty + motorized valves with 3850
VA inrush, 700 VA opening, 250 VA holding
65VA pilot duty + motorized valves with 3850
VA inrush, 700 VA opening, 250 VA holding
65VA pilot duty + motorized valves with 3850
VA inrush, 700 VA opening, 250 VA holding
2A Pilot Duty
17
CB FALCON
a
Main Valve
750-265