CleaverBrooks CFC-500 Operation, Service And Parts Manual page 78

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Section 4 — CFC Commissioning
Parameter Group
Parameter Name
Domestic HW Configuration
DHW setpoint
Domestic HW Configuration
DHW TOD setpoint
Domestic HW Configuration
DHW on hysteresis
Domestic HW Configuration
DHW off hysteresis
Domestic HW Configuration
DHW P gain
Domestic HW Configuration
DHW I gain
Domestic HW Configuration
DHW D gain
Domestic HW Configuration
DHW hysteresis step time
Domestic HW Configuration
DHW modulation sensor
Domestic HW Configuration
DHW priority source
Domestic HW Storage
Configuration
DHW storage enable
Domestic HW Storage
Configuration
DHW storage time
Domestic HW Storage
Configuration
DHW storage setpoint
Domestic HW Storage
Configuration
DHW storage on hysteresis
Domestic HW Storage
Configuration
DHW storage off hysteresis
Domestic HW Storage
Configuration
DHW priority method
Burner Control Ignition
Lightoff rate
Burner Control Ignition
Ignition source
Burner Control Ignition
Ignitor on during
Burner Control Ignition
Pilot type
Burner Control Ignition
Preignition time
Pilot Flame Est. Period
Burner Control Ignition
(PFEP)
Main Flame Est. Period
Burner Control Ignition
(MFEP)
Burner Control Ignition
Flame threshold
Burner Control Flame Failure
Ignite failure response
Burner Control Flame Failure
Ignite failure retries
Burner Control Flame Failure
Ignite failure delay
Burner Control Flame Failure
MFEP flame failure response
Burner Control Flame Failure
Run flame failure response
Burner Control Interlocks
Purge rate proving
Burner Control Interlocks
Lightoff rate proving
Burner Control Interlocks
Interlock start check enable
Burner Control Interlocks
Interlock open response
Interrupted air switch (IAS)
Burner Control Interlocks
enable
Burner Control Interlocks
LCI enable
Burner Control Interlocks
PII enable
Burner Control Interlocks
ILK bounce detection enable
Burner Control Timings & Rates Prepurge rate
Burner Control Timings & Rates Postpurge rate
Burner Control Timings & Rates Standby rate
Burner Control Timings & Rates Prepurge time
Burner Control Timings & Rates Run stabilization time
Burner Control Timings & Rates Postpurge time
Modulation (System)
Configuration
Modulation Output
4-8
Table 4-1 CFC default parameter settings
Min.
Access*
Range
User
32
Service
32
Service
Service
Service
Service
Service
Service
Service
Service
User
Service
User
32
Service
Service
Service
Service
1000
Read Only
Read Only
Read Only
Service
Read Only
Hidden
OEM
0.5
Service
Service
Service
Hidden
Read Only
OEM
Service
Hidden
Read Only
Service
Read Only
Service
Service
OEM
4000
Service
1000
Service
1000
Service
15
Service
Service
15
Read Only
Max.
Default Setting
Range
130
180
120
180
2
5
80
2
15
80
0
25
400
0
25
400
0
0
400
0
60
900
Auto: DHW sensor (S6)
or Outlet (S3S4)
DHW heat demand
Disabled
0
1800
14400
140
180
2
5
80
2
15
80
Drop DHW after priority
time expires
1800
3000
External ignitor
On throughout PFEP
Direct Burner Ignition
0
0
900
4
NA
0.8
5
Lockout
1
30
Lockout
Lockout
Fan speed
Fan speed - except
during ignition
No ILK Check
Lockout
Enable during purge &
ignition
Enabled
Disabled
Enabled
4000
6500
2000
6500
1000
6500
15
900
0
5
900
15
900
VSD Fan PWM
Parameter
Units
Installation Setting
°F
°F
°F
°F
seconds
seconds
°F
°F
°F
RPM
seconds
seconds
seconds
V or μA
seconds
RPM
RPM
RPM
seconds
seconds
seconds
Part No. 750-263
Modbus
Register
(dec)
0453
0454
0455
0456
0457
0458
0459
0460
0461
0463
0504
0505
0506
0507
0508
0509
0197
0224
0226
0227
0232
0233
0234
0250
0239
0240
0241
0242
0243
0229
0230
0237
0238
0246
0248
0249
0253
0196
0198
0207
0231
0235
0236
0192