Section 4 — CFC Commissioning
Parameter Group
Parameter Name
Lead Lag add stage
Lead Lag Configuration
detection time 1
Lead Lag add stage error
Lead Lag Configuration
threshold
Lead Lag add stage rate
Lead Lag Configuration
offset
Lead Lag add stage
Lead Lag Configuration
interstage delay
Lead Lag drop stage method
Lead Lag Configuration
1
Lead Lag drop stage
Lead Lag Configuration
detection time 1
Lead Lag drop stage error
Lead Lag Configuration
threshold
Lead Lag drop stage rate
Lead Lag Configuration
offset
Lead Lag drop stage
Lead Lag Configuration
interstage delay
Lead Lag Configuration
Lead rotation time
Lead Lag Configuration
Force lead rotation time
Lead Lag Configuration
Boiler off options
Lead Lag Configuration
All boilers off threshold
Lead Lag CH ODR min.
Lead Lag Configuration
outdoor temperature
Lead Lag CH ODR low water
Lead Lag Configuration
temperature
Lead Lag CH ODR maximum
Lead Lag Configuration
off point
Lead Lag CH ODR min.
Lead Lag Configuration
water temperature
Lead Lag CH outdoor reset
Lead Lag Configuration
enable
Shaded parameters are Safety Parameters and require Verification and manual reset of the control prior to operation. Please refer to Section A, "Changing
parameter settings".
*Access Levels:
Read Only = parameter not configurable
OEM = manufacturer only
Service = password required (default password is 9220)
User = no password required
4-14
Table 4-1 CFC default parameter settings
Min.
Access*
Range
Service
60
Service
Service
-100
Service
180
Service
Service
60
Service
Service
-100
Service
180
Service
Service
Service
Service
Service
-40
Service
Service
32
Service
Service
Max.
Default Setting
Range
300
5
20%
100
900
Firing rate threshold
300
10
-3%
100
900
1
24
1
168
All Boilers Off option
disabled
25
0
140
80
180
194
230
80
230
Disabled
Parameter
Units
Installation Setting
seconds
°F
%
seconds
seconds
°F
%
seconds
hours
hours
°F
°F
°F
°F
°F
Part No. 750-263
Modbus
Register
(dec)
0716
0718
0719
0722
0723
0725
0727
0728
0731
0733
0734
0736
0737
0518
0519
0521
0527
0548