CleaverBrooks CFC-500 Operation, Service And Parts Manual page 290

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

CB FALCON MODBUS COMMUNICATION
Table 4. CB Falcon Modbus register map
01CE
0462
01CF
0463
01D0
0464
01D1
0465
01D2
0466
01D3
0467
01D4
0468
01D5
0469
01D6
0470
01D7
0471
01D8
0472
01D9
0473
01DA
0474
01DB
0475
01DC
0476
01DD
0477
01DE
0478
01DF
0479
01E0
0480
01E1
0481
01E2
0482
01E3
0483
01E4
0484
RESERVED
DHW priority source
LIMITS CONFIGURATION
Outlet high limit setpoint
Outlet high limit response
Stack limit enable
Stack limit setpoint
Stack limit response
Stack limit delay
Delta-T inlet/outlet enable
Delta-T inlet/outlet degrees R/W
Delta-T response
Delta-T delay
DHW high limit enable
DHW high limit setpoint
DHW high limit response
CH slow start enable
DHW slow start enable
Slow start ramp
Slow start setpoint
Outlet T-rise enable
Outlet T-rise degrees
Outlet T-rise delay
Outlet high limit enable
R/W
U16
0=Disable DHW priority,
1=DHW priority begins when DHW heat demand starts
R/W
U16
SAFETY parameter
-40°-130° (0.1°C precision)
R/W
U16
SAFETY parameter
0=Lockout, 1=Recycle&hold
R/W
U16
SAFETY parameter
0=Disable stack limit,
1=Enable dual sensor safety stack limit,
2=Enable single sensor non-safety stack limit
R/W
U16
SAFETY parameter
-40°-130° (0.1°C precision)
R/W
U16
SAFETY parameter
0=Lockout, 2=Recycle&delay
R/W
U16
SAFETY parameter
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
Delta-T limit for inlet to outlet flow:
0=Disable Delta-T limit,
1=Enable Delta-T limit,
2=Enable Inversion detection,
3=Enable Delta-T limit and Inversion detection
U16
Temperature delta between inlet & outlet sensors when
Delta-T limit occurs:
0°-130° (0.1°C precision)
R/W
U16
0=Lockout,
1=Recycle&delay,
2=Recycle&delay with retry limit
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
SAFETY parameter
0=Disable DHW high limit, 1=Enable dual sensor safety
DHW high limit,
2=Enable single sensor non-safety DHW high limit
R/W
U16
SAFETY parameter
-40°-130° (0.1°C precision)
R/W
U16
SAFETY parameter
0=Lockout, 2=Recycle&hold,
3=Suspend DHW
R/W
U16
0=Disable CH slow start limit,
1=Enable CH slow start limit
R/W
U16
0=Disable DHW slow start limit,
1=Enable DHW slow start limit
R/W
U16
RPM/min or %/min
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
0=Disable outlet T-rise limit,
1=Enable outlet T-rise limit
R/W
U16
Degrees/min (0.1°C precision)
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
0=Disable Outlet high limit, 1=Enable dual sensor safety
Outlet high limit,
2=Enable single sensor non-safety Outlet high limit
20
f
:
a
f
:
f
:
f
:
a
f
:
f
:
a
f
:
f
:
a
f
:
c
a
a