CleaverBrooks CFC-500 Operation, Service And Parts Manual page 294

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

CB FALCON MODBUS COMMUNICATION
Table 4. CB Falcon Modbus register map
022D
0557
022E
0558
022F
0559
0230
0560
0231
0561
0232
0562
0233
0563
0234
0564
0235
0565
0236
0566
0237
0567
0238
0568
0239
0569
023A
0570
023B
0571
023C
0572
023D
0573
023E
0574
023F
0575
0241
0577
Lead Lag CH setpoint
source
Lead Lag modulation sensor R/W
Lead Lag modulation
backup sensor
Lead Lag CH 4 mA water
temperature
Lead Lag CH 20 mA water
temperature
Lead Lag CH Modbus
setpoint
Lead Lag CH Modbus STAT R/W
Slave mode
Slave command
Base load rate
Fan during off cycle rate
Slave sequence order
Lead Lag Modbus port
Slave demand to firing delay R/W
Slave capacity
Base load common rate
Rate allocation method
Lead allocation method
Lag allocation method
EXTENDED CH
CONFIGURATION
CH Modbus STAT
R/W
U16
0=Local setpoint
(register 546),
1=Modbus setpoint
(register 562),
2=4-20mA setpoint
(register 15)
U16
Sensor used for Lead Lag modulation:
0=S5 sensor,
1=S10 sensor
R/W
U16
Backup sensor used for Lead Lag modulation:
0=No backup sensor,
1=Outlet sensor from lead boiler,
2=Average Outlet sensor from all slave boilers
R/W
U16
Temperature corresponding to 4mA signal input:
-40°-130° (0.1°C precision)
R/W
U16
Temperature corresponding to 20mA signal input:
-40°-130° (0.1°C precision)
R/W
U16
-40°-130° (0.1°C precision)
U16
0=No call for heat,
1=Call for heat
R/W
U16
0=Use first according to priority,
1=Equalize run-time,
2=Use last according to priority
R/W
U16
Bit map:
15=Slave demand request,
14=Slave suspend startup,
13=Slave run fan request,
12=Turn on auxiliary pump X,
11=Turn on auxiliary pump Y,
10=Turn on auxiliary pump Z,
9=Reserved (always 0),
8=Commanded rate is binary fraction %
7-0=Commanded rate
R/W
U16
RPM or %
R/W
U16
RPM or %
R/W
U16
0-255
R/W
U16
Modbus port for Lead Lag control:
0=No port assigned,
1=MB1 (Local Modbus) port,
2=MB2 (Global Modbus) port
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
MBH (Million BTU / hour) units
R/W
U16
0=Disabled,
1-100% (in 0.1% units)
R/W
U16
0=Parallel common base limited
R/W
U16
0=Sequence order rotation,
1=Lowest measured run time
R/W
U16
0=Sequence order rotation,
1=Lowest measured run time
R/W
U16
Modbus call for heat (see register 209):
0=No call for heat,
1=Call for heat
24
a
a
a
h
c
c
b
g
,

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cfc-2500Cfc-750Cfc-1000Cfc-1500Cfc-1800

Table of Contents