CleaverBrooks CFC-500 Operation, Service And Parts Manual page 230

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

CB FALCON
Code
3
Internal fault: Hardware fault
4
Internal fault: Safety Relay key feedback
error
5
Internal fault: Unstable power (DCDC)
output
6
Internal fault: Invalid processor clock
7
Internal fault: Safety relay drive error
8
Internal fault: Zero crossing not detected
9
Internal fault: Flame bias out of range
10
Internal fault: Invalid Burner control state
11
Internal fault: Invalid Burner control state flag
12
Internal fault: Safety relay drive cap short
13
Internal fault: PII shorted to ILK
14
Internal fault: HFS shorted to LCI
15
Internal fault: Safety relay test failed due to
feedback ON
16
Internal fault: Safety relay test failed due to
safety relay OFF
17
Internal fault: Safety relay test failed due to
safety relay not OFF
18
Internal fault: Safety relay test failed due to
feedback not ON
19
Internal fault: Safety RAM write
20
Internal fault: Flame ripple and overflow
21
Internal fault: Flame number of sample
mismatch
22
Internal fault: Flame bias out of range
23
Internal fault: Bias changed since heating
cycle starts
24
Internal fault: Spark voltage stuck low or high
25
Internal fault: Spark voltage changed too
much during flame sensing time
26
Internal fault: Static flame ripple
27
Internal fault: Flame rod shorted to ground
detected
28
Internal fault: A/D linearity test fails
29
Internal fault: Flame bias cannot be set in
range
30
Internal fault: Flame bias shorted to adjacent
pin
31
Internal fault: SLO electronics unknown error
32-46
Internal fault: Safety Key 0 through 14
System Errors
47
Flame Rod to ground leakage
48
Static flame (not flickering)
49
24VAC voltage low/high
750-265
Table 49. Falcon Lockout and Hold Codes. (Continued)
Description
Recommended Troubleshooting of Lockout Codes
Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.
1. Check the Module and display connections.
2. Check the Module power supply and make sure that
both frequency, voltage and VA meet the specifications.
106
NOTE
H
H
H
H
H
H
H
L
L
H
H or L
H or L
L
L
L
L
L
H
H
H
H
H
H
H
H
H
H
H
H
L
H
H
H