Table 4. CB Falcon Modbus register map
0050
0080
0051
0081
0052
0082
0053
0083
0054
0084
0055
0085
0056
0086
0057
0087
0058
0088
0059
0089
005A
0090
005B
0091
005C
0092
005D
0093
DOMESTIC HOT WATER
(DHW) STATUS
DHW status
DHW setpoint source
DHW priority count
DHW heat demand
DHW burner demand
DHW requested rate
DHW frost heat demand
DHW frost burner demand
Active DHW on hysteresis
Active DHW off hysteresis
DHW storage time
DHW storage heat demand R
DHW storage burner
demand
PUMP STATUS
Pump A status
R
U16
0=Unknown,
1=Disabled,
2=Normal,
3=Suspended
R
U16
0=Unknown,
1=Normal setpoint,
2=TOD setpoint,
5=DHW tap setpoint,
6=DHW preheat setpoint
R
U16
Countdown of time when DHW has priority over CH
(secs). Applicable when DHW priority time is enabled
(see register 452).
R
U16
0=Off,
1=On
R
U16
0=Off,
1=On
R
U16
c
RPM or %
R
U16
0=Off,
1=On
R
U16
0=Off,
1=On
R
U16
0°-130° (0.1°C precision)
R
U16
0°-130° (0.1°C precision)
R
U16
Elapsed DHW storage time (secs)
U16
0=Off,
1=On
R
U16
0=Off,
1=On
R
U16
Bit map:
Demand:
15-14=Reserved,
13=Auxiliary 2 pump demand,
12=Auxiliary 1 pump demand,
11=System pump demand,
10=Boiler pump demand,
9=DHW pump demand,
8=CH pump demand
Reason:
7=Reserved,
6=Pump assigned to logical pump,
5=Pump exercise requested,
4=On due to exercise,
3=On due to overrun,
2=Forced off,
1=Forced on,
0=On due to normal demand