CleaverBrooks CFC-500 Operation, Service And Parts Manual page 287

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Table 4. CB Falcon Modbus register map
011B
0283
011C
0284
011D
0285
011E
0286
011F
0287
0120
0288
0121
0289
0122
0290
0123
0291
0124
0292
0125
0293
0126
0294
0127
0295
0128
0296
0129
0297
012A
0298
Boiler pump overrun time
Auxiliary 1 pump output
Auxiliary 1 pump control
RESERVED
System pump output
System pump control
System pump overrun time
Pump exercise interval
Pump exercise time
CH pump start delay
Boiler pump start delay
System pump start delay
Auxiliary 1 pump start delay R/W
CH pump options 1
CH pump options 2
DHW pump options 1
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
0=None, 1=Pump A, 2=Pump B, 3=Pump C
R/W
U16
0=Auto, 1=On
R/W
U16
0=None, 1=Pump A, 2=Pump B, 3=Pump C
R/W
U16
0=Auto, 1=On
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
Days
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
R/W
U16
Bit map:
15=Normal pump demand when auxiliary pump Z is set,
14=Normal pump demand when auxiliary pump Y is set,
13=Normal pump demand when auxiliary pump X is set,
12-7=Reserved (always 0),
6=Normal pump demand when DHW service is active,
5=Normal pump demand when CH service is active,
4=Reserved,
3=Normal pump demand when DHW demand,
2=Normal pump demand when CH demand,
1=Normal pump demand when local burner demand,
0=Local demand inhibited for faults
R/W
U16
Bit map:
15=Pump used for Lead Lag,
14=Pump used for local demand,
13-9=Reserved (always 0),
8=Force pump off when DHW high limit,
7=Force pump off when DHW anti-condensation,
6=Force pump off when CH anti-condensation,
5=Force pump off when DHW priority is active,
4=Force pump on when DHW frost protection,
3=Force pump on when CH frost protection,
2=Force pump on when Lead Lag slave demand,
1=Force pump on when local burner demand,
0=Force pump on when Outlet high limit
R/W
U16
Bit map:
15=Normal pump demand when auxiliary pump Z is set,
14=Normal pump demand when auxiliary pump Y is set,
13=Normal pump demand when auxiliary pump X is set,
12-7=Reserved (always 0),
6=Normal pump demand when DHW service is active,
5=Normal pump demand when CH service is active,
4=Reserved,
3=Normal pump demand when DHW demand,
2=Normal pump demand when CH demand,
1=Normal pump demand when local burner demand,
0=Local demand inhibited for faults
17
CB FALCON MODBUS COMMUNICATION