CB FALCON MODBUS COMMUNICATION
Table 4. CB Falcon Modbus register map
005E
0094
005F
0095
0060
0096
0061
0097
0062
0098
0063
0099
0064
0100
0065
0101
0066
0102
0067
0103
0068
0104
0069
0105
006A
0106
006B
0107
006C
0108
006D
0109
006E
0110
006F
0111
0070
0112
0071
0113
0072
0114
0073
0115
0074-0076 0116-0118 RESERVED
0077
0119
0078-007F 0120-0127 RESERVED
Pump B status
CH pump start delay time
CH pump status
CH pump overrun time
CH FP overrun time
CH pump idle days count
DHW pump status
DHW pump start delay time R
DHW pump overrun time
DHW FP overrun time
DHW pump idle days count R
System pump status
System pump overrun time
System pump idle days
count
Boiler pump status
Boiler pump overrun time
Boiler pump idle days count R
Auxiliary 1 pump status
Auxiliary 1 pump idle days
count
Auxiliary 2 pump status
Auxiliary 2 pump overrun
time
Auxiliary 2 pump idle days
count
Auxiliary 1 pump overrun
time
R
U16
Bit map:
Demand:
15-14=Reserved,
13=Auxiliary 2 pump demand,
12=Auxiliary 1 pump demand,
11=System pump demand,
10=Boiler pump demand,
9=DHW pump demand,
8=CH pump demand
Reason:
7=Reserved,
6=Pump assigned to logical pump,
5=Pump exercise requested,
4=On due to exercise,
3=On due to overrun,
2=Forced off,
1=Forced on,
0=On due to normal demand
R
U16
Running delay time before CH pump will be turned on.
R
U16
For application build less than 1600 see table 12. For
application build 1600 or higher see table 13
R
U16
Running overrun time for CH pump (seconds)
R
U16
Running overrun time for CH pump due to frost
protection (seconds)
R
U16
Number of days that CH pump has not run (sat idle).
R
U16
For application build less than 1600 see table 12. For
application build 1600 or higher see table 13
U16
Count down (seconds) when DHW pump is delayed from
starting.
R
U16
Running overrun time for DHW pump (seconds)
R
U16
Running overrun time for DHW pump due to frost
protection (seconds)
U16
Number of days that DHW pump has not run (sat idle).
R
U16
For application build less than 1600 see table 12. For
application build 1600 or higher see table 13
R
U16
Running overrun time for Lead Lag pump (seconds)
R
U16
Number of days that LL pump has not run (sat idle).
R
U16
For application build less than 1600 see table 12. For
application build 1600 or higher see table 13
R
U16
Running overrun time for Boiler pump (seconds)
U16
Number of days that boiler pump has not run (sat idle).
R
U16
For application build less than 1600 see table 12. For
application build 1600 or higher see table 13
R
U16
Number of days that auxiliary 1 pump has not run (sat
idle).
R
U16
See table 13.
R
U16
Running overrun time for auxiliary 2 pump (seconds)
R
U16
Number of days that auxiliary 2 pump has not run (sat
idle).
R
U16
Running overrun time for auxiliary 1 pump (seconds)
10
e
e.
e
.
e
.
e
.