Section 2 — Installation
Nominal
Actual I.D.
Length in feet
10
20
30
40
50
60
70
80
90
100
125
150
175
200
**Fuel: Natural Gas
**Inlet Pressure: Less than 2.0 psi
**Pressure Drop: 0.30" w.c.
**Specific Gravity: 0.60
2-18
Table 2-4: Gas Line Capacity - Schedule 40 Metallic Pipe
1"
1-1/4"
1.04
1.380"
9
**Maximum Capacity in Cubic Feet of Gas per Hour (cfh)
514
1,060
363
726
284
583
243
499
215
442
195
400
179
368
167
343
157
322
148
304
131
269
119
244
109
209
102
185
Pipe Size
1-1/2"
2"
2-1/2"
1.610"
2.067"
2.469"
1,580
3,050
4,860
1,090
2,090
3,340
873
1,680
2,680
747
1,440
2,290
662
1,280
2,030
600
1,160
1,840
552
1,060
1,690
514
989
1,580
482
928
1,480
455
877
1,400
403
777
1,240
366
704
1,120
336
648
1,030
313
602
960
3"
4"
3.068"
4.026"
8,580
17,500
5,900
12,000
4,740
9,660
4,050
8,290
3,590
7,330
3,260
6,640
3,000
6,110
2,790
5,680
2,610
5,330
2,470
5,040
2,190
4,460
1,980
4,050
1,820
3,720
1,700
3,460
Part No. 750-263