CleaverBrooks CFC-500 Operation, Service And Parts Manual page 77

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

• Burner Control Interlocks
• Burner Control Timings & Rates
• Burner Control Ignition
• Burner Control Flame Failure
• System Configuration
• Fan Configuration
• Lead Lag Configuration
Parameter Group
Parameter Name
System ID & Access
Boiler Name
System ID & Access
Installation data
System ID & Access
OEM Identification
System ID & Access
Installer password
System ID & Access
Modbus address
System ID & Access
Factory data
Central Heat Configuration
CH enable
Central Heat Configuration
CH demand source
Central Heat Configuration
CH modulation sensor
Central Heat Configuration
CH setpoint
Central Heat Configuration
CH TOD setpoint
Central Heat Configuration
CH on hysteresis
Central Heat Configuration
CH off hysteresis
Central Heat Configuration
CH outdoor reset enable
Central Heat Configuration
CH P gain
Central Heat Configuration
CH I gain
Central Heat Configuration
CH D gain
Central Heat Configuration
CH hysteresis step time
Central Heat Configuration
CH setpoint source
Central Heat Configuration
CH modulation source
Central Heat Configuration
CH has priority over LL
Central Heat Configuration
CH 4mA water temperature
Central Heat Configuration
CH 20mA water temperature
CH ODR max. outdoor
Outdoor Reset Configuration
temperature
CH ODR min. outdoor
Outdoor Reset Configuration
temperature
CH ODR low water
Outdoor Reset Configuration
temperature
Outdoor Reset Configuration
CH ODR maximum off point
Minimum boiler water
Outdoor Reset Configuration
temperature
Domestic HW Configuration
DHW enable
Domestic HW Configuration
DHW demand switch
DHW priority has priority over
Domestic HW Configuration
CH
DHW priority has priority over
Domestic HW Configuration
LL
Domestic HW Configuration
DHW priority override time
Part No. 750-263
Table 4-1 CFC default parameter settings
Min.
Access*
Range
Service
Service
Read Only
Service
Service
Read Only
Service
Service
Service
User
32
User
32
Service
Service
Service
Service
Service
Service
Service
Service
Service
Service
Service
Service
Service
-40
Service
-40
Service
32
Service
32
Service
32
User
Service
Service
Service
Service
Max.
Default Setting
Range
Boiler 1
SERIAL NUMBER
CB FALCON 833-
03639
9220
0
1
250
Enabled
Stat terminal
Modulation from Outlet
sensor (S3S4)
150
194
120
194
2
5
60
2
15
60
Disabled
0
25
400
0
25
400
0
0
400
0
60
900
Local SP
Local Modulation (PID)
No
60
180
80
140
0
140
80
180
194
210
80
180
Disabled
DHW switch (S6) or
sensor only
Yes
Yes
0
1800
14400
Section 4 — CFC Commissioning
Parameter
Units
Installation Setting
°F
°F
°F
°F
seconds
°F
°F
°F
°F
°F
seconds
Modbus
Register
(dec)
0183
0184
0185
0190
????
????
0208
0209
0210
0211
0212
0213
0214
0215
0216
0217
0218
0219
0578
0580
0582
0583
0584
0512
0513
0514
0516
0526
0448
0449
0450
0451
0452
4-7