CleaverBrooks CFC-500 Operation, Service And Parts Manual page 234

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

CB FALCON
Code
136
Interrupted Airflow Switch failed to close
137
ILK failed to close
138-142
RESERVED
FAULT CODES 149 THROUGH 165 ARE
OEM SPECIFIC FAULT CODES.
143
Internal fault: Flame bias out of range 1
144
Internal fault: Flame bias out of range 2
145
Internal fault: Flame bias out of range 3
146
Internal fault: Flame bias out of range 4
147
Internal fault: Flame bias out of range 5
148
Internal fault: Flame bias out of range 6
149
Flame detected
150
Flame not detected
151
High fire switch ON
152
Combustion pressure ON
153
Combustion Pressure Off
154
Purge Fan switch On
155
Purge Fan switch Off
155
Purge fan switch OFF
750-265
Table 49. Falcon Lockout and Hold Codes. (Continued)
Description
Recommended Troubleshooting of Lockout Codes
1. Check wiring and correct any possible wiring errors.
2. Check Interrupted Airflow switch(es) to assure proper
function.
3. Verify voltage through the airflow switch to the IAS input
with a voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the
module.
1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure proper
function.
3. Verify voltage through the interlock string to the interlock
input with a voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the
module.
OEM Specific
1. Holds if flame detected during Safe Start check up to
Flame Establishing period.
OEM Specific
1. Sequence returns to standby and restarts sequence at
the beginning of Purge after the HF switch opens. if flame
detected during Safe Start check up to Flame Establishing
period.
OEM Specific
1. Check wiring and correct any potential wiring errors.
2. Check High Fire Switch to assure proper function (not
welded or jumpered).
3. Manually drive the motor to the High Fire position and
adjust the HF switch while in this position and verify
voltage through the switch to the HFS input with a
voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the
module.
OEM Specific
1. Check wiring and correct any errors.
2. Inspect the Combustion Pressure Switch to make sure it
is working correctly.
3. Reset and sequence the relay module.
4. During STANDBY and PREPURGE, measure the
voltage between Terminal J6-5 and L2 (N). Supply voltage
should be present. If not, the lockout switch is defective
and needs replacing.
5. If the fault persists, replace the relay module.
OEM Specific
1. Purge fan switch is on when it should be off.
110
NOTE
H
H
L
L
L
L
L
L
H or L
H
H or L
H or L
H or L
H or L
H
H or L