CB FALCON MODBUS COMMUNICATION
Table 4. CB Falcon Modbus register map
00CF
0207
00D0
0208
00D1
0209
00D2
0210
00D3
0211
00D4
0212
00D5
0213
00D6
0214
00D7
0215
00D8
0216
00D9
0217
00DA
0218
00DB
0219
00DC
0220
00DD
0221
00DE
0222
00DF
0223
00E0
0224
00E1
0225
00E2
0226
00E3
0227
00E4
0228
Standby rate
CH CONFIGURATION
CH enable
CH demand switch
CH modulation sensor
CH setpoint
CH time of day setpoint
CH on hysteresis
CH off hysteresis
CH outdoor reset enable
CH P-gain
CH I-gain
CH D-gain
CH hysteresis step time
CH pressure setpoint
CH pressure on hysteresis
CH pressure off hysteresis
RESERVED
BURNER CONTROL
CONFIGURATION
Ignition source
BLR/HSI function
Igniter on during
Pilot type
Flame sensor type
R/W
U16
SAFETY parameter
RPM or %
R/W
U16
0=Disable Central Heating,
1=Enable Central Heating
R/W
U16
Source for CH demand:
0=Modulation sensor only,
1=STAT terminal,
2=EnviraCOM remote Stat,
3=LCI,
4=Reserved,
5=Modbus STAT
R/W
U16
Sensor used for CH modulation:
0=Outlet sensor,
2=Inlet sensor,
3=S5 sensor,
4=S10 sensor
R/W
U16
-40°-130° (0.1°C precision)
R/W
U16
-40°-130° (0.1°C precision)
Setpoint when Time Of Day switch is on.
R/W
U16
0°-130° (0.1°C precision)
R/W
U16
0°-130° (0.1°C precision)
R/W
U16
0=Disable outdoor reset, 1=Enable outdoor reset
R/W
U16
0-1000
R/W
U16
0-1000
R/W
U16
0-1000
R/W
U16
0-64800 seconds (0=Disable hysteresis stepping)
R/W
U16
0-150psi (0.1psi precision)
R/W
U16
0-150psi (0.1psi precision)
R/W
U16
0-150psi (0.1psi precision)
R/W
U16
SAFETY parameter
0=Internal ignition, 1=External ignition,
2=Hot Surface Igniter (HSI)
R/W
U16
SAFETY parameter
BLR/HSI terminal function:
0=blower motor,
1=Hot Surface Igniter (HSI)
R/W
U16
SAFETY parameter
0=All Pilot Flame Establishing Period (PFEP),
1=First ½ of PFEP
R/W
U16
SAFETY parameter
0=Interrupted, 1=Intermittent,
2=Direct burner ignition (constant ignition),
3=Direct burner ignition (pulsed ignition)
R/W
U16
SAFETY parameter
0=None (no sensor)
1=Flame rod,
2=UV power tube,
3=UV power tube, ignore flame during ignition