CleaverBrooks CFC-500 Operation, Service And Parts Manual page 235

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Code
Description
156
Combustion pressure and Flame ON
157
Combustion pressure and Flame OFF
158
Main valve ON
159
Main valve OFF
160
Ignition ON
161
Ignition OFF
162
Pilot valve ON
163
Pilot valve OFF
164
Block intake ON
165
Block intake OFF
166-171
RESERVED
Feedback
172
Main relay feedback incorrect
173
Pilot relay feedback incorrect
174
Safety relay feedback incorrect
175
Safety relay open
176
Main relay ON at safe start check
177
Pilot relay ON at safe start check
178
Safety relay ON at safe start check
179-183
RESERVED
Parameter Faults
184
Invalid BLOWER/HSI output setting
185
Invalid Delta T limit enable setting
186
Invalid Delta T limit response setting
187
Invalid DHW high limit enable setting
188
Invalid DHW high limit response setting
189
Invalid Flame sensor type setting
190
Invalid interrupted air switch enable setting
191
Invalid interrupted air switch start check
enable setting
192
Invalid igniter on during setting
193
Invalid ignite failure delay setting
Table 49. Falcon Lockout and Hold Codes. (Continued)
Recommended Troubleshooting of Lockout Codes
OEM Specific
1. Check that flame is not present in the combustion
chamber. Correct any errors.
2. Make sure that the flame detector is wired to the correct
terminal.
3. Make sure the F & G wires are protected from stray
noise pickup.
4. Reset and sequence the module, if code reappears,
replace the flame detector.
OEM Specific
1. Check Main Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, replace
the module.
OEM Specific
1. Check Ignition terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, replace
the module.
OEM Specific
1. Check Pilot Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, replace
the module.
OEM Specific
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it is
working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the voltage across
the switch. Supply voltage should be present. If not, the
Block Intake Switch is defective and needs replacing.
5. If the fault persists, replace the relay module.
Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.
1. Return to Configuration mode and recheck selected
parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
111
CB FALCON
NOTE
H or L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
750-265