CleaverBrooks CFC-500 Operation, Service And Parts Manual page 232

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

CB FALCON
Code
80
DHW high limit
81
Delta T limit
82
Stack limit
83
Delta T exchanger/outlet limit
84
Delta T inlet/exchanger limit
85
Inlet/outlet inversion limit
86
Exchanger/outlet inversion limit
87
Inlet/exchanger inversion limit
88
Outlet T-rise limit
89
Exchanger T-rise limit
90
Heat exchanger high limit
Sensor Faults
91
Inlet sensor fault
92
Outlet sensor fault
93
DHW sensor fault
94
Header sensor fault
95
Stack sensor fault
96
Outdoor sensor fault
97
Internal Fault: A2D mismatch.
98
Internal Fault: Exceeded VSNSR voltage
99
Internal Fault: Exceeded 28V voltage
tolerance
100
Pressure Sensor Fault
750-265
Table 49. Falcon Lockout and Hold Codes. (Continued)
Description
Recommended Troubleshooting of Lockout Codes
1. Check wiring and correct any possible errors.
2. Replace the DHW high limit.
3. If previous steps are correct and fault persists, replace
the module.
1. Check Inlet and Outlet sensors and pump circuits for
proper operation.
2. Recheck the Delta T Limit to confirm proper setting.
3. If previous steps are correct and fault persists, replace
the module.
1. Check wiring and correct any possible errors.
2. Replace the Stack high limit.
3. If previous steps are correct and fault persists, replace
the module.
1. Check wiring and correct any possible errors.
2. Replace the Inlet sensor.
3. If previous steps are correct and fault persists, replace
the module.
1. Check wiring and correct any possible errors.
2. Replace the Outlet sensor.
3. If previous steps are correct and fault persists, replace
the module.
1. Check wiring and correct any possible errors.
2. Replace the DHW sensor.
3. If previous steps are correct and fault persists, replace
the module.
1. Check wiring and correct any possible errors.
2. Replace the header sensor.
3. If previous steps are correct and fault persists, replace
the module.
1. Check wiring and correct any possible errors.
2. Replace the stack sensor.
3. If previous steps are correct and fault persists, replace
the module.
1. Check wiring and correct any possible errors.
2. Replace the outdoor sensor.
3. If previous steps are correct and fault persists, replace
the module.
Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.
1. Verify the Pressure Sensor is a 4-20ma source.
2. Check wiring and correct any possible errors.
3. Test Pressure Sensor for correct operation.
4. Replace the Pressure sensor.
5. If previous steps are correct and fault persists, replace
the module.
108
NOTE
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H or L
H
H
H
H
H
H
L
L
L
H