CleaverBrooks CFC-500 Operation, Service And Parts Manual page 282

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

CB FALCON MODBUS COMMUNICATION
Table 4. CB Falcon Modbus register map
00A3
0163
00A4
0164
00A5
0165
00A8
0168
00A9
0169
00AA
0170
00AB
0171
00AC
0172
00AD
0173
00AE
0174
00AF
0175
00B0
0176
00B1
0177
00B2
0178
00B3
0179
Lead Lag master heat
demand
Lead Lag slave burner
demand
Lead Lag slave requested
rate
EXTENDED PUMP
STATUS
Pump C status
RESERVED
EXTENDED SENSOR
STATUS
Outdoor temperature
Outdoor sensor state
Outlet T-rise rate
Exchanger T-rise rate
S10 sensor reading
S10 sensor state
SYSTEM
CONFIGURATION
Product type
Password
Temperature units
Antishort cycle time
R
U16
0=Off,
1=On
R
U16
0=Off,
1=On
R
U16
RPM or %
R
U16
Bit map:
Demand:
15-14=Reserved,
13=Auxiliary 2 pump demand,
12=Auxiliary 1 pump demand,
11=System pump demand,
10=Boiler pump demand,
9=DHW pump demand,
8=CH pump demand
Reason:
7=Reserved,
6=Pump assigned to logical pump,
5=Pump exercise requested,
4=On due to exercise,
3=On due to overrun,
2=Forced off,
1=Forced on,
0=On due to normal demand
R
U16
-40°-130° (0.1°C precision)
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
R
U16
Outlet temperature change rate (degrees/second, 0.1°C
precision)
R
U16
Heat exchanger temperature change rate (degrees/
second, 0.1°C precision)
R
U16
-40°-130° (0.1°C precision)
R
U16
0=None, 1= Normal, 2=Open, 3=Shorted, 4=Outside
high range, 5=Outside low range, 6=Not reliable
R
U16
Product family (MSB):
0=Unknown product,
1=Hydronic boiler control,
2=Steam boiler control,
3=Reserved,
4=Fulton pulse hydronic boiler control,
5=Fulton pulse steam boiler control,
6=Cleaver Brooks hydronic boiler control,
7=Cleaver Brooks steam boiler control
Product ID (LSB):
0=Residential control,
1=Commercial control
W
Variable length password string (up to 20 characters)
requesting Falcon permission to write registers.
R/W
U16
Display format for temperature at user interface:
0=°F (Fahrenheit),
1=°C (Celsius)
R/W
U16
0-64800 seconds (18 hours), 0xFFFF=Not configured
12
c
b
a

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cfc-2500Cfc-750Cfc-1000Cfc-1500Cfc-1800