CleaverBrooks CFC-500 Operation, Service And Parts Manual page 186

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

CB FALCON
TERMINAL TABLE
A1
J6 TERMINAL 2
A2
J6 TERMINAL 1
LCI
J6 TERMINAL 3
A3
J7 TERMINAL 6
A4
J7 TERMINAL 5
A5
J7 TERMINAL 4
ILK
J5 TERMINAL 1
A6
J7 TERMINAL 3
PII
J6 TERMINAL 5
A7
J7 TERMINAL 2
A8
J7 TERMINAL 1
L1
Sorting
Annunciator items are sorted first by their category
assignment. The category order is:
LCI, ILK, PII, Other (Unused items appearing in the Other
category)
Within the category, inputs are sorted by the input identifier
(A1–A8), with the additional rule that LCI (if enabled) is last in
the LCI category, ILK last in the ILK category, and PII (if
enabled) is last in the PII category.
Viewing the System Display using the "programmable"
annunciator display in this case would resemble Fig. 27.
750-265
MASTER
WATER
LIMIT CONTROL
SWITCH
LEVEL
STACK
HIGH GAS
LOW GAS
VENT
PRESSURE
PRESSURE
PII
PII
V1
V2
DOOR
COMPRESSOR
Fig. 26. Example of annunciator inputs and terminal names.
FALCON
ANNUNCIATOR NAMES
A1
MASTER SWITCH
A2
WATER LEVEL
LCI
LIMIT CONTROL
A3
STACK VENT FAN
A4
HIGH GAS PRESSURE
A5
LOW GAS PRESSURE
ILK
AIRFLOW SWITCH
AIRFLOW
A6
UPSTREAM VALVE
PII
DOWNSTREAM VALVE
A7
SECURITY DOOR
A8
AIR COMPRESSOR
Fig. 27. Annunciator display.
If A7 is defined as a HFS input, then the parameter that calls it
a "Security door" would be ignored and the automatic value
(High Fire Switch) is used instead (the same would be true for
the A8 LFS and A1 IAS).
62