CleaverBrooks CFC-500 Operation, Service And Parts Manual page 106

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Section 5 — Service and Maintenance
Single Electrode
3/8" E1/16"
5-4
the source of a problem. This information is accessed through the
Lockout History.
2. Remedy condition that caused lockout to occur.
3. Reset control by pressing <Clear Lockout> from the Lockout History
screen.
Light-off Problems
The distance between the flame rod and the burner (mantle) should
be 3/8". The dimensions on both the booster ignitors and the flame
rod are not easily adjustable - bending the rods can cause damage
to the insulation material. In addition, a bent electrode will return
to its original shape when heated. If an electrode or flame rod is out
of specification, replacement is generally required. Clean or replace
as necessary.
Also see Troubleshooting Chart below.
Electrode spacing for the booster ignitor should be 1/8".
The distance of the nearest booster ignitor electrode to the mantle
is approximately 7/8".
Sight Glass
Dual Electrode
7/8" E1/16"
Burner Canister
Figure 5-5 Electrode spacing
1/8"
Part No. 750-263