CleaverBrooks CFC-500 Operation, Service And Parts Manual page 303

Clearfire condensing boiler
Hide thumbs Also See for CFC-500:
Table of Contents

Advertisement

Table 8. Falcon lockout and hold codes
81
Delta T inlet/outlet limit
82
Stack limit
83
Delta T exchanger/outlet limit
84
Delta T inlet/exchanger limit
85
Inlet/outlet inversion limit
86
Exchanger/outlet inversion limit
87
Inlet/exchanger inversion limit
88
Outlet T-rise limit
89
Exchanger T-rise limit
90
Heat exchanger high limit
91
Inlet sensor fault
92
Outlet sensor fault
93
DHW sensor fault
94
S2 (J8-6) sensor fault
95
Stack sensor fault
96
S5 (J8-11) sensor fault
97
Internal fault: A2D mismatch
98
Internal fault: Exceeded VSNSR
voltage tolerance
99
Internal fault: Exceeded 28V
voltage tolerance
100
Pressure sensor fault
101-104 RESERVED
105
Flame detected out of sequence
106
Flame lost in MFEP
107
Flame lost early in run
108
Flame lost in run
109
Ignition failed
110
Ignition failure occurred
111
Flame current lower than WEAK
threshold
112
Pilot test flame timeout
113
Flame circuit timeout
114-121 RESERVED
122
Lightoff rate proving failed
123
Purge rate proving failed
124
High fire switch OFF
125
High fire switch stuck ON
126
Low fire switch OFF
127
Low fire switch stuck ON
Table 8. Falcon lockout and hold codes
Hold/
128
Fan speed failed during prepurge
Lockout
Hold/
129
Fan speed failed during preignition
Lockout
130
Fan speed failed during ignition
Hold/
Lockout
Hold/
131
Fan movement detected during standby Hold
Lockout
132
Fan speed failed during run
Hold/
133-135 RESERVED
Lockout
136
Interrupted Airflow Switch failed to close Hold
Hold/
137
ILK failed to close
Lockout
138-142 RESERVED
Hold/
Lockout
143
Internal fault: Flame bias out of range 1
Hold/
144
Internal fault: Flame bias out of range 2
Lockout
145
Internal fault: Flame bias out of range 3
Hold/
146
Internal fault: Flame bias out of range 4
Lockout
147
Internal fault: Flame bias out of range 5
Hold/
Lockout
148
Internal fault: Flame bias out of range 6
Hold
149
Flame detected
Hold
150
Flame not detected
Hold
151
High fire switch ON
Hold
Hold
152
Combustion pressure ON
Hold
Lockout
153
Combustion pressure OFF
Lockout
154
Purge fan switch ON
Lockout
155
Purge fan switch OFF
Hold
156
Combustion pressure and Flame ON
Hold/
157
Combustion pressure and Flame OFF
Lockout
158
Main valve ON
Lockout
159
Main valve OFF
Lockout
160
Ignition ON
Lockout
161
Ignition OFF
Lockout
162
Pilot valve ON
Hold
163
Pilot valve OFF
Hold
164
Block intake ON
Lockout
165
Block intake OFF
Lockout
166-171 RESERVED
172
Main relay feedback incorrect
Lockout
173
Pilot relay feedback incorrect
Lockout
174
Safety relay feedback incorrect
Hold
175
Safety relay open
Hold
176
Main relay ON at safe start check
Hold
177
Pilot relay ON at safe start check
Hold
178
Safety relay ON at safe start check
179-183 RESERVED
33
CB FALCON MODBUS COMMUNICATION
Hold/
Lockout
Hold/
Lockout
Hold/
Lockout
Hold
Hold
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Hold/
Lockout
Hold
Hold/
Lockout
Hold/
Lockout
Hold/
Lockout
Hold/
Lockout
Hold/
Lockout
Hold/
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout
Lockout