Code
Description
50
Modulation fault
51
Pump fault
52
Motor tachometer fault
53
AC inputs phase reversed
54
Safety GVT model ID doesn't match
application's model ID
55
Application configuration data block CRC
errors
56-57
RESERVED
58
Internal fault: HFS shorted to IAS
59
Internal Fault: Mux pin shorted
Normal Event Status
60
Internal Fault: HFS shorted to LFS
61
Anti short cycle
62
Fan speed not proved
63
LCI OFF
64
PII OFF
65
Interrupted Airflow Switch OFF
66
Interrupted Airflow Switch ON
67
ILK OFF
68
ILK ON
69
Pilot test hold
70
Wait for leakage test completion
71-77
RESERVED
78
Demand Lost in Run
79
Outlet high limit
Table 49. Falcon Lockout and Hold Codes. (Continued)
Recommended Troubleshooting of Lockout Codes
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
3. If fault persists, replace module.
1. Check the Module and display connections.
2. Check the Module power supply and make sure that
both frequency and voltage meet the specifications.
3. On 24Vac applications, assure that J4-10 and J8-2 are
connected together.
Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.
Will not be a lockout fault. Hold Only.
1. Check wiring and correct any faults.
2. Check Interlocks connected to the LCI to assure proper
function.
3. Reset and sequence the module; monitor the LCI status.
4. If code persists, replace the module.
1. Check wiring and correct any faults.
2. Check Preignition Interlock switches to assure proper
functioning.
3. Check the valve operation.
4. Reset and sequence the module; monitor the PII status.
5. If code persists, replace the module.
1. Check wiring and correct any possible shorts.
2. Check airflow switches to assure proper functioning.
3. Check the fan/blower operation.
4. Reset and sequence the module; monitor the airflow
status.
5. If code persists, replace the module.
1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure proper
function.
3. Verify voltage through the interlock string to the interlock
input with a voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the
1. Verify Run/Test is changed to Run.
2. Reset Module.
3. If fault repeats, replace module.
1. Internal Fault. Reset Module.
2. If fault repeats, replace module.
1. Check wiring and correct any possible errors.
2. If previous steps are correct and fault persists, replace
the module.
1. Check wiring and correct any possible errors.
2. Replace the Outlet high limit.
3. If previous steps are correct and fault persists, replace
the module.
107
CB FALCON
NOTE
H
H
H
L
L
L
L
L
L
H
H
H
H or L
H or L
H or L
H or L
H or L
H
H
H
H or L
750-265