DC link components
8.6 Control Supply Module CSM
Table 8- 24
Signaling contact without terminal connector in
the delivery condition
8.6.3.4

X24 24 V terminal adapter

Table 8- 25
X24 24 V terminal adapter
Terminal
+
M
Type: Screw terminal 5 (Page 755)
Max. cross-section that can be connected: 6 mm
The 24 V terminal adapter is included in the scope of supply.
8.6.3.5

S1 DIP switch

Table 8- 26
DIP switch S1
Terminal
1
2
It is only permissible to changeover when in the no-voltage state.
562
Installing the signaling contact
Designation
24 V power supply
Ground
2
Designation
Changeover switch, single
operation / parallel operation
Dummy contact
(not used)
Signaling contact, complete with terminal
connector
Technical data
Supply voltage 24 ... 28.8 V DC
Electronics ground
Technical data
Left: Single operation
Right: Parallel operation
Changing over the output characteristic