X1 Line Connection - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Line Modules Booksize
4.9 Smart Line Modules with external air cooling
4.9.3.2

X1 line connection

Table 4- 74
X1: Line connection for Smart Line Modules 5 kW and 10 kW
For ring cable lugs without insulation
1)
Table 4- 75
X1: Line supply connection for Smart Line Modules 16 kW
For ring cable lugs without insulation
1)
304
Terminal
Technical data
U1
Supply voltage:
3 AC 380 ... 480 V, 50 / 60 Hz
V1
Type: Screw terminal 5 (Page 755)
W1
Max. cross-section that can be connected: 6 mm
Tightening torque: 1.2 ... 1.5 Nm
PE connection
Threaded hole M5 / 3 Nm
Terminal
Technical data
U1
Supply voltage:
3 AC 380 ... 480 V, 50 / 60 Hz
V1
Type: Screw terminal 6 (Page 755)
W1
Max. cross-section that can be connected: 10 mm
Tightening torque: 1.5 ... 1.8 Nm
PE connection
Threaded hole M5 / 3 Nm
1
1
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
2
2