NOTICE
Damage to the drive electronics when switching the line contactor under load
When switching the line contactor (type according to the recommended selection) under
load, then the contacts will be subject to premature wear. This can cause the contactor to
malfunction, with subsequent damage to the drive electronics.
• Use a leading opening auxiliary contact or use a Voltage Sensing Module (VSM10).
• If this is not possible, then avoid switching the line contactor under load.
Danger to life due to electric shock in the event of voltage flashovers at the temperature
sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Use temperature sensors that fully comply with the specifications of the safety isolation.
• If safe electrical separation cannot be guaranteed (for linear motors or third-party
4.4.2.4

X24 24 V terminal adapter

Table 4- 27
Type: Screw terminal 5 (Page 755)
Max. cross-section that can be connected: 6 mm
The 24 V terminal adapter is included in the scope of supply.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
WARNING
motors, for example), use a Sensor Module External (SME120 or SME125) or Terminal
Module TM120.
X24: 24 V terminal adapter
Terminal
+
M
4.4 Active Line Modules with cold plate
Designation
Technical data
24 V power supply 24 V DC supply voltage
Ground
Electronics ground
2
Line Modules Booksize
203