DC link components
8.6 Control Supply Module CSM
8.6.8

Technical data

Table 8- 28
Technical data
6SL3100-1DE22-0AA1
Input data, AC input
Line voltage
Line frequency
Rated input current
Rated value (at V
)
E rated
Starting current inrush
Input data, DC input
Rated input voltage
Input voltage range
DC link voltage
(continuous input voltage)
Supply current (at 600 V)
Overvoltage tripping
Undervoltage tripping
Output data
Rated output voltage V
A rated
Rated output current I
A rated 1)
Rated output power P
A rated
Overcurrent limitation for short-circuit
Surge suppression
Current carrying capacity of the 24 V busbar
Residual ripple (clock frequency approx. 50 kHz)
Switching peaks (bandwidth 20 MHz)
Power loss ride-through (at 400 V AC)
Power loss
Line
DC link
(see Power loss tables (Page 781))
Efficiency
Circuit breaker (UL)
Type designation:
Rated current:
Resulting rated short-circuit current
SCCR at 480 V AC:
Fuses (UL)
Class RK1, listed JDDZ
Rated current:
resulting rated short-circuit current
SCCR at 480 V AC:
574
Unit
Value
V
3 AC 380 ... 480 ± 15 %
AC
Hz
45 ... 66
A
≤ 2
AC
A
≤ 28 at > 5 ms
AC
V
600
DC
V
300 ... 882
DC
V
430 ... 800
DC
300 ... 430 < 1 min
800 ... 853 < 1 min
853 ... 882 < 10 s
A
1.1
DC
V
> 882
DC
V
280 ± 3 %
DC
V
24 ... 28.8
DC
A
20
DC
W
520
A
Approx. 23
DC
V
< 35
A
20
DC
mV
< 100
pp
mV
< 200
pp
ms
5
W
70
W
65
%
> 83
3RV1021-1DA10
A
2.2 ... 3.2 (setting value 3)
kA
100
A
6
kA
200
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6