To optimize usage of the external air heat sink, it is best to arrange the components in such
a way that the heat is dissipated equally over the surface of the external heat sink. This
means that, if possible, a large power section should be situated next to a smaller one. The
current carrying capacity of the DC-link busbars must be taken into account here.
Figure 12-36 Rear view of a control cabinet with drive line-up, cold plate and external air heat sink
In this example, two axial fans with a diameter of 150 mm ensure forced convection. The
ribbed heat sink, which is attached to the rear, is located in an air duct (approx. 150 mm
deep). Additional air guides at the sides improve air guidance and significantly optimize the
power unit cooling.
Note
The external heat sink must be sealed with respect to the control cabinet in accordance with
IP65.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Control cabinet
External fan
Air baffle plates
External air heat sink
Cabinet design and EMC Booksize
12.11 Information on cold plate cooling