Cabinet design and EMC Booksize
12.13 Power losses of the components
Table 12- 42 Coefficients to calculate the power loss in the control cabinet for externally cooled Motor
Motor Module
Single Motor Module 3 A
Single Motor Module 5 A
Single Motor Module 9 A
Single Motor Module 18 A
Single Motor Module 30 A
Single Motor Module 45 A
Single Motor Module 60 A
Single Motor Module 85 A
Single Motor Module 132 A
Single Motor Module 200 A
Double Motor Module 3 A
Double Motor Module 5 A
Double Motor Module 9 A
Double Motor Module 18 A
Overview of typical power losses at the rated operating point
Table 12- 43 Typical power losses in the control cabinet for operation at the rated operating point for
Motor Module
Single Motor Module 3 A
Single Motor Module 5 A
Single Motor Module 9 A
Single Motor Module 18 A
Single Motor Module 30 A
Single Motor Module 45 A
Single Motor Module 60 A
Single Motor Module 85 A
Single Motor Module 132 A
Single Motor Module 200 A
Double Motor Module 3 A
Double Motor Module 5 A
Double Motor Module 9 A
Double Motor Module 18 A
794
Modules for typical applications
internally and externally cooled Motor Modules
a [W]
S
[W/A]
1
10
2,30
10
2,30
10
2,30
10
2,34
16
1,29
21
1,31
27
1,37
32
1,37
50
1,06
50
1,06
15
1,37
15
1,37
15
1,37
18
1,56
P
[W]
Vn
internal air cooling
26
36
60
140
263
382
550
772
1257
2032
54
81
152
281
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
S
[W/A
]
2
2
0,100
0,100
0,100
0,101
0,057
0,015
0,006
0,006
0,004
0,004
0,240
0,240
0,240
0,056
P
[W]
Vn
external air cooling
18
24
39
85
106
110
130
192
260
422
28
41
79
110
Booksize Power Units