Line Modules Booksize
4.8 Smart Line Modules with internal air cooling
Internal air cooling
Rated power
DC link capacitance
Smart Line Module
Drive line-up, max.
Power factor
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit current
SCCR
3)
Cooling method (internal air
cooling)
Sound pressure level
Cooling air requirement
Max. permissible heat sink
temperature
Weight
The specified power ratings apply to the line voltage range from 380 V to 480 V.
1)
For 16 kW and 36 kW Smart Line Modules: Default for 400 V line supplies; undervoltage trip threshold is adjusted to the
2)
parameterized rated voltage.
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
3)
Module in the drive system.
Values cannot be read out by the system (STARTER).
4)
296
6SL3130–
6AE15–0Axx
kW
5
μF
220
μF
6000
cos ϕ
0,98
See Section Overcurrent protection using line fuses and circuit breakers
(Page 51)
kA
65
Internal fan
dB(A)
< 60
m
/h
29,6
3
° C
69
4)
Rated voltage for rated data 3 AC 380 V
kg
4,7
6AE21–0Axx
6TE21-6Axx
10
16
330
705
6000
20000
65
65
< 60
< 60
29,6
56
73
77
4)
4,8
7
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
6TE23-6Axx
6TE25-5AAx
36
55
1410
1880
20000
20000
65
65
< 65
< 60
112
160
80
75
10
17